TBUK15051

National Tower Blocks Network, Annual Spot Safety Survey

ARCHIVE DOCUMENT
Not stated
November 1990

3.04 Many fire doors are broken or not fully operative. They
have closer springs ripped off, missing handles, broken hinges
or they are so jammed that they will not open or close
properly. In some cases doors are missing. (see chart).
3.05 One lobby showed signs of a recent fire. This fire door
was locked. This is illegal.
3.06 At the lowest level where the fire brigade would connect
their pump the dry riser cover had been ripped off. This allows
the dry riser to be vandalised and has obvious safety
consequences. Damage to the dryriser could mean the fire
brigade carrying hoses etc up the block. Such a delay could
prove fatal. (fire in Merry Hill Court Birmingham 13 vii 1990)
3.07 In the ground floor entrance hall the wall mounted lift
panel has been vandalised. The cover is missing. Bare live
wires are exposed within reach of children.
3.08 The false ceiling in this area which is 4" (100mm) deep is
generally vandalised has missing tiles. Above these are exposed
electrical cables running alongside what appears to be water
pipes. It is possible to touch these cables.The height of the
tiles is 2100 mmor about 7'0".
3.09 Only 20% of the flats are occupied, 80% are empty and of
these 40% had their doors swinging open. There are many
breakins and vandalism is rife. Apart from the major fire risk
there is risk from damage to water pipes causing flooding to
the flats below and a major risk of explosion because these
flats have gas supplies.
3.10 Each floor has a store opening onto the main lobby off
which are three flats. Although these are lockable most were
left open. Some were full of debris or old furniture. They
appear to be a possible fire risk.
3.11 There are no smoke alarms and no notices instructing
tenants what to do in the event of a fire.
3.12 We understand that these flats have been refurbished
within the last three years. Their present state is potentially
lethal. The conditions in the other three blocks on the estate
is according to the Chairman of the Tenants Association as bad
if not worse. There was not time to inspect these three blocks
and River Bank Towers was chosen at random.

4.00 CONCLUSIONS.

4.01 There are major fire safety defects in this building. A
number of fire doors are inoperative. In the event of a fire
this situation would allow large amounts of smoke and hot
possibly lethal fumes to hazard the escape routes. Tenants and
rescue services could become trapped and overcome in the very
area where they should be safest.

4.02 The high number of empty flats has led to high levels of
vandalism and breakins. There are no instructions on what to do
in a fire, many lights are broken, there is no emergency
lighting, fire doors broken and some are locked.

4.03 There is an understandable level of insecurity among the
tenants. There are 80% of the flats empty. Of these 40% have
been forced open. This block was apparently refurbished three
years ago.

4.04 With the high levels of vandalism we are seriously
concerned about the risk of an explosion from the gas supply.

4.05 River Bank Towers is one of four similar blocks on the
estate. The conditions in the other three blocks are equally as
bad if not worse according to the Chair of the Tenants
Association.

Sam Webb Architect.
October 26th 1990.
Copyright.

TBUK15051