TBUK15049

National Tower Blocks Network, Annual Spot Safety Survey

ARCHIVE DOCUMENT
Not stated
November 1990

4.00 THE INSPECTION.

4.01 We started the inspection on the 21st floor walking down
the fire stairs. Not all floors were visited but enough was
seen to give an overall view.

4.02 21st floor: the fresh air vents at both the West and East
ends of the corridor are broken and in a dangerous state. The
space of all those inspected was full of rubbish which in some
cases created a serious fire risk. The grating at the west end
has been broken, possibly by children jumping on it. A hole is
thus exposed through which it would be possible for a small
child to fall 200' 0" to the ground. This is very dangerous and
this condition is found on many floors. Objects can be thrown
through this hole endangering people at ground level. The door
to the Dry Riser has no lock for security and is an open
invitation for vandalism. In a recent fatal fire in Birmingham
Dry Risers had been vandalised and water had to be pumped from
ground level for the full height of the building. As a result
the fire took longer to bring under control. The same condition
applies to many service duct doors in the corridors. Some of
these contain gas supplies.

4.03 19th floor: the fresh air vent at the East end was full of
rubbish. The service duct doors were not secure.

4.04 17th floor: the fresh air vent at the East end had rubbish
and parts of a car in it.

4.05 15th floor: both vents were filthy and full of rubbish.
The fire door leading to the corridor would not shut. The top
hinge had been badly repaired with #10 30mm Pozidrive screws.
All of the screws were loose and could be pulled out by hand.
These screws are recent.

4.06 13th floor: both vents were filthy.

4.05 8th floor: The fire door from the stairs will not close.
The hinge is loose. The vents at the East and West ends are
loose. The floors between the 13th and 8th were not inspected
or between 6th and 2nd.

4.06 2nd floor: the firedoor from the stair would not shut. The
ducts were filthy and there had been a fire in one. The service
ducts were not secure.

4.07 Ground level: there is a ramp from the fire escape door to
the ground. The staircase is ventilated by three slots.
Immediately adjacent is timber panelling on battens fixed to
brickwork. There is a 50mm gap behind the panelling. This
panelling constitutes a fire risk and would hazard the escape
stair. The corner of the panelling has been broken away.

5.00 CONCLUSIONS.

5.01 These flats have a piped gas supply. In the event of a
leak in the supply pipe there is no way for the gas to vent
except into the corridor. Gas supply pipes should not be in an
unvented duct.

5.02 A number of fire doors are inoperative. In the event of a
fire they would allow large amounts of smoke and hot, possibly
lethal fumes to hazard escape routes. The use of timber
panelling at ground level is questionable. It could pose a
serious threat to the safety of the occupants by filling the
escape stair with smoke and fumes if it was set alight by
vandals. It has already been damaged.

5.03 Many of the fresh air vents to the escape corridors have
been vandalised. They are in an unsafe condition. They are
accesible to children who could fall through the gap at floor
level.

5.04 Many fires are caused by vandalism. Rubbish frequently
collects in spaces such as the areas at the base of the timber
panelling. A fire here could cause a great deal of smoke which
would be drawn through the lower fresh air vent to the escape
stair and hazard people using the stair.

5.05 Sporle Court which has a gas supply for cooking and
central heating appears to be of Large Panel Construction. If
this is the case is then it is extremely doubtful if the
structure is capable of sustaining a 5psi explosion without
progressive collapse. Was this block checked in 1968 or again
when the Minister requested in October 1984 that Large Panel
Blocks be checked for safety? It is very important that this
matter is verified by the Council. Are there any other similar
blocks on this estate or elsewhere in the borough?

5.06 Sporle Court as inspected on Friday 14th September 1990:

**** does not appear to meet the basic requirements of BSCP
CP3: Chap IV(1962) with regard to Means of Escape

**** appears to be of Large Panel Construction with a gas
supply. No evidence of strengthening could be found. This poses
a serious question. Is Sporle Court safe in the event of a gas
explosion or will it suffer progressive collapse?

COPYRIGHT.
Sam Webb architect. 081 472 6652.
Report on behalf of the National Tower Blocks Network.
September 1990.

TBUK15049
49 of 57