2.03 cont'd:
"It is, of course, essential that there should be adequate
physical separation between the two occupancies and that the
means of escape from the dwellings should be designed and
constructed so that they can under no circumstances be attacked
by fire or smoke from the other occupancy."

"The guiding principle in the recommendations which follow is
safety of life. In securing this, means of escape, construction
and firefighting all play a part. This part of the Code deals
with all three subjects, but reccommendations on constructions
have not been fully developed as many aspects are already
subject to building control."

Quoted from the Introduction of Chap IV (1962).

2.04 Means of Escape from each floor is from the front door of
each flat via the fire escape stair to the ground. There is no
secondary means of escape as would be the case if these flats
had been designed and built today. Therefore it is imperative
that these areas are as safe as is humanly possible.

2.05 Due to the age of these flats there will be a high
percentage of asbestos used in the construction.

3.00 THE INSPECTION.

3.01 We started the inspection on the top floor walking down
the fire stairs.

3.02 There are four flats per floor. These open onto a central
internal ventilated lobby served by lifts. The ventilation is
inadequate. Each lift serves alternate floors. This lobby opens
onto a ventilated space. Off this is a glazed room containing a
rubbish shute and the fire stairs. These are ventilated.

3.03 In terms of its original planning Knighthead Point meets
the requirements of BSCP CP3: ChapIV (1962). In practice these
are NOT met and the block is defective in many respects. In the
event of a fire the safety of the tenants would be seriously
compromised. In quite a small fire escaping tenants could be
overcome by smoke in the very areas where there should be no
smoke; in the fire stairs and escape lobbies themselves.
Tenants could die in such a situation. The reason for this is
as follows.

3.04 A considerable number of fire doors are defective. They
either do not close properly, or have missing glazing or in
many cases the doors have completely been removed. It appears
that this situation is not recent one and these doors have been
inoperative for some time. In some cases for AS LONG AS FOUR
YEARS. Although we did not inspect the other three 22 storey
blocks I have reason to believe similar conditions will be
found in there as well.

3.05 A number of the doors which have been replaced do not shut
properly and jam against the floor. These require the simple
operation of easing up or they too will become totally broken.

3.06 Because the ventilation to the internal lobby is
inadequate some landings become smelly so tenants prop the fire
doors open to get rid of the smell. This is a dangerous
practice.

3.06 There are no smoke alarms in public areas.

3.07 There is no emergency lighting system for the public
areas. In the event of a fire which immobilises the lighting
system then all the public areas; fire stairs, lobbies etc
would be plunged into darkness.

4.00 CONCIERGE SYSTEM.

4.01 There is a concierge system in operation. Visitors are
asked to sign in and out. Lifts have cameras behind sloping
black glass and in other areas there are cameras.

4.02 This had led to a considerable reduction in vandalism and
break-ins. We were told that this had come about through
tenants who were leaseholders (approx 40%) refusing to pay
their service charge (£1,000 pa). These are tenants who
exercised their 'right to buy'.

4.03 It is difficult to see why the concierge has not picked up
the problems of broken fire doors. If he had a 'report back
system' to the Housing Department then these matters could be
picked up when they occur. It is in no ones interest to have
broken fire doors in any building. The implications for the
council and its officers could be very serious in the event of
a fatality in a fire.

5.00 INSTRUCTIONS TO TENANTS

5.01 There are no instructions to tenants about what to do in a
fire. In view of what happened in the recent fire in
Birmingham, the high temperatures which develop in a normal
domestic fire, ie +1000 deg C and the speed with which fires
develop, then this is a serious omission which must be
rectified.

5.02 If this building was an hotel then such notices would have
to be displayed. These instructions should not just be printed
in English. They should cover all ethnic groups. They should be
prominantly displayed in all public areas. This should be
carried out in all blocks throughout the borough.