tbuk15043

National Tower Blocks Network, Annual Spot Safety Survey

ARCHIVE DOCUMENT
Not stated
November 1990

3.04 In the event of a fire the safety of the tenants would be
seriously compromised. In quite a small fire escaping tenants
could be overcome by smoke in the very areas where there should
be no smoke; in the fire stairs and escape lobbies themselves.
Tenants could die in such a situation. The reason for this is
as follows.

3.05 A considerable number of fire doors are defective. They
either do not close properly, have no glass, broken closers, no
handles or safe exit in an emergency is impeded by broken
refuse chute covers which are just lying in the lobby.

3.06 Of the 11 floors we inspected only floors 10, 7, 2 and 1
had no defects.

3.07 Major defects were found on the following floors: 11-1
fire door, 9- 2 fire doors plus broken glazing and a broken
rubbish chute cover, 8- 2 fire doors, 6- 1 fire door and a
broken rubbish chute cover, 5- 2 fire doors and broken glazing
and a broken refuse chute cover, 4- 1 fire door and glazing, 3-
2 fire doors.

3.08 It appears that this situation is not a recent one and
these doors have been inoperative for some considerable time.
Although we did not inspect the other five blocks we have
reason to believe that equally serious safety defects will be
found in them as well.

3.09 There was a notice at the bottom of the stairs warning
against the use of LPG in the flats.

3.10 There is no emergency lighting in this block.

3.11 We did not inspect any flats.

4.00 CONCLUSIONS

4.01 Block "E" fails to meet the basic requirements of BSCP
CP3: Chap IV (1962) with regard to Means of Escape.

4.02 In the event of a fire the fire stair and escape lobbies
could become seriously smoke logged. This could cause loss of
life and would make fighting any fire more difficult. It could
put the lives of the rescue services at risk.

4.04 There is no alternative Means of Escape from each flat. If
this block was designed today this would be a legal
requirement. Therefore it is imperative that the fire escape
areas are made as safe as is humanly possible.

4.05 There are no instructions to tenants about what to do in a
fire. If this was a hotel these would be required by law.
Notices in English as well as for ethnic minorities should be
clearly displayed throughout the public areas of all these
blocks.

4.06 Emergency lighting should be installed in all lobbies and
the fire stair.

4.07 Smoke alarms should be fitted in these areas.

Sam Webb Architect for The National Tower Blocks Network
COPYRIGHT September 1990.