TBUK15041

National Tower Blocks Network, Annual Spot Safety Survey

ARCHIVE DOCUMENT
Not stated
November 1990

6. Robert Shaw House fails to meet the basic requirements of BSCP
CP3: Chap IV (1962) or the Building Regulations with respect to the
surface spread of flame of materials used in the construction of the
false ceilings in the lobbies and the fire stair.

7. Spring, Norfolk Park, fails to meet the basic requirements of BSCP
CP3: Chap IV (1962) with respect to the surface spread of flame of
materials used in the construction of the false ceilings in the lobbies
and the fire stair.

There is no alternative means of escape from each flat in five of the
blocks surveyed; Block ‘E’, Kedge House, Knighthead Point, River Bank
Towers and Robert Shaw. If designed today a secondary means of escape
would be a legal requirement. Therefore it is imperative that the fire
escape areas in the one means of escape are safe.

In two of the blocks; Kedge House and Knighthead Point, we found metal
door grills installed by tenants. Because of the high number of break-
ins to flats many tenants have fitted their own security devices,
including metal doors. The conflict between fire safety and security is
an important point in an fire safety work carried out in tower blocks.
This point has been recognised in the proposed amendments to the
Building Regulations 1985:
“In blocks of flats there is a potential for conflict between the need
for easy and rapid evacuation of a building in case of fire and the
control of entry and exit in the interests of security. Measures to
prevent unauthorised access can also hinder fire service entry to
rescue people trapped by fire. It is important that any potential
conflicts be identified and resolved at the design stage and not left to
ad hoc expedients after completion.”
(Quote from Part B: Safety in Fire para 0.14 p6 issued by the DOE for
comment on 19th March 1990.)

PART THREE

NATIONAL TOWER BLOCKS NETWORK
RECOMMENDATIONS

1. Tower blocks should be subject to fire
certification. This would ensure that standards of safety
were regularly inspected by the fire brigade and that landlords
were required to comply with their instructions by law.

Fire certification would ensure that blocks were properly
maintained by the landlord, that the means of escape would be
kept clear and that fire doors, vents etc would be maintained and
repaired whenever necessary.

Fire certification would require instructions to be provided to
each tenant and in the communal areas as to what to do in the
event of a fire.

2. Fire drills should be carried out at regular intervals, at
least once a year.

3. Smoke alarms should be provided by the landlord for each
flat and for the communal areas. These alarms should be
maintained by the landlord.

4. Internal gas supplies should be removed from all large
panel system tower blocks as a matter of extreme urgency. The
government should again call on local authorities to inspect such
blocks within their ownership and should oversee these
inspections.

5. Each tower block should have a log book in which any
work, of whatever nature, is recorded by the responsible
department. So that when future work was necessary on the
tower block the log book would contain information concernings
dates, type of materials used and the extent of work carried out.

TBUK15041
41 of 57