National Tower Blocks Network, Annual Spot Safety Survey

SURVEY OF ROBERT SHAW HOUSE: OCTOBER 8TH 1990
Robert Shaw House on the Netherthorpe Estate in Sheffield was built
between 1958 and 1960. It is a fourteen storey block which appears to
be constructed of reinforced concrete with brick panels. The
block contains four flats on each floor, which lead off a central lobby.
The lobby contains two lifts serving alternative floors and two fire
escape stairs. Each flat has only one means of escape through the front
door to the lobby and escape stairs, though each flat has its own balcony
which contains the rubbish chute.
Robert Shaw was built before the fire regulations, BSCP CP3 Chap IV
(1962) came into force, however the block fails to meet some of the
standards set within these regulations. There has been recent work
on upgrading the fire doors, all of which were in working order at
the time of the inspection.
On certain floors the windows on the fire escape staircases were either
broken, jammed open or closed due to paint. There is a dryriser on
alternative floors, which though not covered all looked in good repair.
However, despite the recent fire safety work carried out on the block,
which has included fire safety doors on all the flats, there are no smoke
alarms, no emergency lighting and no fire alarms. There were some fire
notices but not on every floor.
The major cause of concern during the inspection was the material used
to line the ceilings of the lobbies and the soffits of the stairs in the
fire escape stairwell. The tiles are made of compressed fibre, some
are damaged. A small piece of one tile was tested with the use of a
match, it burned.
In the main lobby on the ground floor the ceiling was covered in
polystyrene tiles, it is well known that polystyrene burns readily
giving off dense black smoke, which contains toxic fumes. In some of
the common areas there appears to be wooden casings around pipe ducts
and exposed pipe lagging was found. These also constitutes a fire risk.
Robert Shaw does not meet the fire regulations in respect of surface
spread of flame of materials used in construction of false ceilings in
the lobbies and stairwells, which constitute the only means of escape.
A SUMMARY OF OUR FINDINGS
Each of the seven tower blocks surveyed by the National Tower Blocks
Network fail to meet either the Building Regulations or the British
Standards Codes of Practice in reference to buildings above a certain
height:
1. Block 'E' on the Broadmead Road Estate fails to meet the basic
requirements of BSCP CP3: Chap IV (1962) with regards to means of
escape. In a fire the fire stair and escape lobbies could become
seriously smokelogged due to broken doors.
2. Kedge House fails to meet the basic requirements of BSCP CP3: Chap
IV (1962) with regards to:
(a) A one hour fire separation of tenancies.
(b) Means of escape.
A number of fire doors, glazed panels and rubbish chute covers are
broken and the fire stair and escape lobbies could become seriously
smokelogged due to broken doors.
3. Knighthead Point fails to meet the basic requirements of BSCP CP3:
Chap IV (1962) with regards to means of escape, due to missing and
broken doors. The fire stair and escape lobbies could become seriously
smokelogged due to broken doors.
4. Sporle Court fails to meet the basic requirements of BSCP CP3: Chap
IV (1962) with regards to means of escape. A number of fire doors are
inoperative and the use of timber panelling at ground level could pose a
serious threat to tenants by filling the escape stair with smoke and
fumes. There are signs of vandalism in the block and many fires are
caused by vandalism. Rubbish often collects at the base of timber
panelling and should this catch light, smoke would be drawn through the
fresh air vent into the escape stair.
It seems doubtful that Sporle Court, which is of Large Panel
Construction could withstand a 5 p.s.i. explosion without progressive
collapse. Sporle Court has a piped gas supply running up an unvented
duct, therefore in the event of a leak the gas will vent into the corridor.
5. River Bank Towers fails to meet the basic requirements of BSCP CP3:
Chap IV (1962) with regards to means of escape due to broken and
locked fire doors. The fire stair and escape lobbies could become
seriously smokelogged due to broken doors.