IMG_0983

Notes on Inquiry

ARCHIVE DOCUMENT
Not stated
1 August 1968

Plucking at a straw from Smedley's point, cooker
falling could have fractured nut. IX. p.56.

3 Non-detection by Miss Hodge.

Burgoyne's evidence (layering) arrived late in the day
and was not cross-examined. Day 7 p. 44 C.

Burgoyne layering requisites:

1 A slow leak - laminar flow.

2 An absence of draught.

(See ventilation evidence Waller of Atkins - JL)

3 Leak to be in upwards direction.

Napier against Burgoyne theory. Day 7, page 37 D.

Moore against Burgoyne, Day 14, page 48.

(Both Moore and Napier asked for time, further investigation - JL)

Cooker totally undamaged .. on debris .. no debris on it.
How did this happen if explosion was behind it?

(Even in final report it was admitted that no-one knows how nut
was broken - JL)

Evidence of witnesses that there was a luminous flame and
dark smoke, carbonaceous in origin, accompanying explosion.
NOT fitting gas explosion.

Admits it is not THE problem; there will always be explosions.
The BUILDING is Tribunal's worry.

Suggests:

1 A code of practice for industrialised buildings.

2 An immediate and detailed appraisal and analysis
of R.P. design and methods of construction to find
best way of strengthening it.

Should Abraham point be occupied?

3 People like gas. Sometimes it's cheaper. North
Sea Gas.

Gas Act 1948 Section 56 (1) Gas Board required to
supply gas to any one within 25 yards of one of
Board's mains.

Section 67, Minister may make such regulations as he
thinks fit to protect people from fire, explosion or
other dangers.

IMG_0983