IMG_0882

Notes on Inquiry

ARCHIVE DOCUMENT
Not stated
19 July 1968

12 (continued)

35 RAH asked by Pu sley if he could calculate lateral pressure
which would cause bolts to bend and fail. "We could."

(but who pays? ratepayers? Not TWA obviously - JL)

Snows have never used this prefab system.
RAH likes steel and concrete - "brick buildings do not resist
wind."

36 Griffiths "Wind tunnel tests necessary?"
RAH "If one is approaching 200'."

Goodfellow "It was a safe structure?"
RAH "Yes."

38 I want to follow, with you, the 'littleboxes' doctrine
that was being put to you before lunch.

39 Goodfellow interrupted by Chairman. "We have had Mr. Hartland's
view on general feasibility .. etc. etc."

Goodfellow"I was using the process of re-examination to try
to understand what has gone before."

40 Goodfellow asks if there might ought to be wind tunnel tests.
Shows photographs of collapse and points out saving of
bedrooms; elicits from RAH "It must be a very effective
joint."

41 RAH "Timber packs, a clumsy feature."

42 VWL. CHAN (Dr.) N.B.A.

Eveleigh "Any regulations, in any country dealing with use of
gas in high storey buildings?"
C: "No, after R.P. I heard of some French regulations."
E: "In U.S.?"
C: "No."

E: "Prefab. panel system in U.S.?"
"I cannot say none, but an insignificant number."

N.B.A. deals with multi-storey construction only in Scotland.

43 N.B.A. has not considered design with L.N. system, not got
round to it. This is the authority (he means responsibility)
of local authority, engineer or district surveyor. (No wonder
he cannot say the word.) "We have approved some of the systems."
Griffiths "Do not give names. Sufficient if we can have that
list copies" (of approved systems).

Explosives not taken into account.