8 The bearing between the conc flr panel
and the supporting wall panel is provided
by conc ribs which project from the ribs
in the floor panel. The p rbs are not resp

9. In collapse, all these ribs broke of in
shear at the face of the bearing wall panel.

10 Prct, the reinf from the floor rib should
proj into the rib and show on the end
face of the component as positive evidence
of its existence. This reinforcement then
provides additional dowel sup at the bearing.

11 A similar precaution is req when detailing
the reinforcement of rotated bearing ribs.

12. Continuity reinforcement is req which
links adjacent panels over the bearing
supports : or other provision to tie the
floor panels from end to end of the block.

Continuity between Adjacent Vert Panels.

13 The wall panels sheared vertically between
the abutting edges thus losing the supporting
beam action of the wall.

14. Preferably the edge junctions should be
reinforced together eg by projecting and
overlapping links between adjacent
wall panels laced tog with a vert tie
rod. This precaution is partic imp at
corners.

LR Creasy
22 May 68

Stab of Precast Conc Work.
1 The inherent stab of insitu conc constrn
is due by the continuity of reinforce
ment between panels.

2 Quite normal proportions provide a
very considerable insurance against
potential collapse from an unexpected