Danielle Gregory, Ledbury Estate Evidence Statement

after the government circulars 62/68 and 71/68. Southwark Council have said that all the
information they had on the blocks, from the handover from the GLC in the early 80's indicated
that they were 'Type B' blocks and didn't require strengthening. They understood now that this
may be incorrect.
As such, ARUP were then asked to undertake further intrusive investigations to detail how the
Ledbury Estate could be brought up to meet the building regulations, though it is understood
piped and bottled gas are never to be reinstated or allowed within the blocks. ARUP have
proposed a structural strengthening project which includes the stripping out of all flats, and
effectively ‘bracing’ the blocks both inside and out with metal beams across ceilings, floors and
walls. Southwark Council will be responsible for the permanent fire stopping solution at the
Ledbury Estate, should the option to be refurbished be chosen. I have serious concerns over
the viability of Southwark Council’s proposed permanent fire stopping solution, which consists of
mastic and fire-resistant backing rod, which would need to be periodically inspected and
renewed. To me, this does not seem satisfactory enough for reinstating a ‘Stay Put’ policy once
works are carried out, and I also have concerns that other local authorities may follow suit in
their own Large Panel tower blocks, especially as there does not appear to be any firm
guidance or regulation currently in place, in regards to fire stopping in Large Panel System
tower blocks prone to thermal movement and compartmentation breaches.
I understand that the former Department for Communities and Local Government wrote to local
authorities with Large Panel System tower blocks, asking them to check their records to ensure
that they are correct and explaining the need to potentially carry out intrusive inspections.
Lannoy Point and Hartopp Point on the Aintree Estate in Hammersmith and Fulham are very
similar to the Ledbury Estate tower blocks, and also part of the ‘Morris Walk’ series. They do not
have a gas supply and had some tensile wiring strengthening undertaken in the 1980’s, but
gaps and cracks have been present in these two blocks for many years too. The London
Borough of Hammersmith and Fulham have now also changed the ‘Stay Put’ policy in these
towers to a ‘Get Out’ policy and employed fire marshals to patrol the blocks, as well as asking
ARUP to undertake similar structural assessments to those done at the Ledbury Estate and we
await the results of these assessments.
I have two grave concerns relating to Large Panel System tower blocks, in particular Taylor
Woodrow Anglian:
1) There is an inherent fire risk in these types of tower blocks. Thermal movement causes
the large panels to bow outwards, especially in warm weather, which opens up a gap at
ceiling and floor level. This breaches compartmentation and means each flat is
connected, one flat to the other. This is something that has been reported in Large Panel
System tower blocks for many years.
2) There may be further Large Panel Systems with a gas supply that poses a risk of
progressive collapse in the event of a gas explosion. Even without a gas supply, these