Fear Over Safety in Glasgow Reema Blocks

FEARS OVER SAFETY IN GLASGOW REEMA BLOCKS
SPeaking on Scottish Television Glasgow District Councils
Assistant Director of Engineering James Smith confirmed fears of
Roystonhill highrise tenants that three metal reclad REEMA blocks
are a major fire risk and subject to Progressive collapse in an
explosion of less than 2.5Psi (17KNms).
Checked in 1969 following the Ronan Point disaster in which 5
People died when the side of the newly built 22 storey east London
block collapsed following a gas explosion Glasgow based consultant
engineers W.A.Fairhurst and Partners Passed Glasgow's blocks as
safe.
Recent checks following the DOE and Scottish Office directive
issued over two years ago in the wake of investigations by Sam
Webb into the notorious London Tower block have revealed that the
three 25 storey Glasgow blocks do not meet the minimum structural
requirements of 2.5 Psi for flats without a gas supply.
Now new strengthening works to bring the blocks up to a minimum of
2.5Psi are being hampered by the lack of constructional drawings
of the original scheme built between 1966 and the early 70's.
Colin Farley the Project Engineer is confident however that this
is not a problem even though he has been told in a Precontact
meeting not to Proceed until reinforcement has been located in the
building. Farley has been told to "eliminate the need for the
contractor to Place cleats by trial and error." He is confident
that this can be done although serious doubts are being raised by
the tenants who have consulted Sam Webb.
SPeaking to tenants, students and council officials Sam Webb
revealed that hitherto secret reports to the Council dated 17th
February 1969 revealed grave doubts by Fairhurst & Ptnrs over the
long term ability of many Glasgow system blocks to withstand wind
loadings expected in their lifetime.
Revealed exclusively in detail to Building Design Fairhurst's 1969
warnings over four Glasgow estates to the Controller of
Engineering Services R P Fleming stated:
*** MARYHILL "B" overstressing on wind loading of 49% above
normal permissible stresses.
*** ROYSTON "B" at 25 storeys these blocks are EVEN MORE
CRITICAL THAN MARYHILL. OVERSTRESSING LEADS TO AN INCREASE
OF 67% ABOVE NORMAL PERMISSIBLE STRESSES FOR DEAD AND LIVE
LOAD ONLY.
*** SPRINGBURN "A" & "B" With the constant working of the
structure in high winds, this severe cracking will become
evident and MAY WELL BE ON A SCALE THAT COULD ALARM THE
OCCUPANTS.
*** In conclusion Fairhurst stated that "a storm of
abnormal severity could cause cracking of structural walls
and MIGHT alarm the occupants of the flats."
*** Fairhurst were UNABLE TO RECOMMEND ANY METHOD OF
STRENGTHENING.