Sam Webb and Charles Wakstein, Comments on the Report Prepared by Assistant Chief Fire Officer

COMMENTS ON THE REPORT PREPARED BY Mr J.E.SLACK, ASSISTANT CHIEF FIRE OFFICER, 28th June 1976, ON ABNORMAL FIRE HAZARDS AT HUNSLET GRANGE.
1.00 Mr Slack does not state how many flats were visited, he just says "several". The number of flats he infact visited was 3.
1.01 Page 2a. Cracks.
Mr Slack found cracks 1mm wide, 3/4" (18 mm) deep.
Webb/Wakstein found cracks of 1 3/4" (44 mm) deep and 1 1/4" (32 mm) deep.
Mr Slack says that heat would not pass through a crack 18mm deep - though there would be smoke seepage. However he does not support these statements with any calculations, and anyway the passage of any smoke does not comply with the Building Regulations E9(1) or E9(2).
1.02 Slack's recommendation on chipping out joints will cause serious weakness in the structure. See para 216 and 148 Ronan Point report. This recommendation shows a deep misunderstanding of the function of these joints, they are not sealing between parts of the structure. They ARE the structure.
2.00 Page 2b. Drypack Failure.
Slack agrees with our reports to Councillor Sparling, and Sam Webb's letter of 25th June 1976. The defects found by us and by Mr Slack do not comply with Regulation E9 (2), and as he states: "Polystyrene burns readily with very heavy smoke propogation". We believe there is a further risk. Mr Slack condemns the service ducts but does not state that he has inspected inside one. On inspection we found that the cores in the ends of the floor slabs are open and we believe that fire can be drawn from the duct through the floor slab.
3.00 Service Ducts. These are a serious fire risk. There is no fire stopping around pipes where they pass through the duct wall and through floors. The duct does not comply with regulation E10, E11 and E 14.
4.00 Bowing of panels. Slack says infill with fire resisting material or replace. How are these panels to be replaced ?
5.00 Calor Gas Explosion. (L.P.G.)
Slack's comment contains a serious error of fact which leads to false assumptions.
5.01 He states: "In my opinion no comparison can be drawn between the effect of the gas explosion in Ronan Point and the possible effect of a single calor gas heater. In the former, towns gas from a virtually unlimited supply was accidently introduced in large quantities and in the case of a calor gas heating appliance the gas cloud would be restricted to that produced from a single cylinder. Should this cylinder be involved in fire my view is that any explosion would vent through the window and the "shrapnel effect" would be contained within the room of origin."
5.02 Slack is wrong in assuming "towns gas from a virtually unlimited supply". When Dr Napier, Senior Lecturer in Department of Chemical Engineering and Chemical Technology at Imperial College was asked what he would have expected to find if the whole flat at Ronan Point had been filled with an explosive gas air mixture - he said "Briefly , Sir, I do not think I would have expected to find a flat." Day 7, 11 July 1968, p 31B transcript.
5.03 There was quite a small amount of gas, 30 - 100 cu ft, which is equivalent to between 1 lb and 4 lbs of gas. The meter was a 1/- (5p) prepay meter (total money in it was 7/-, the flat had been lived in for 3 weeks). The Ronan Point report, para 91 says only 50 cu ft (2 lbs) of gas was the most likely amount. Some of the experts who gave evidence thought it was less than this, for the following reasons:
a) Miss Hodge, the tenant, did not smell any gas.
b) She suffered no gas poisoning.
There are cylinders of Calor Gas containing 32 lbs of gas at Hunslet Grange.
5.04 The explosive force at Ronan Point was in the region of 3 - 12 pounds per square inch. Ronan Point Report page 61 Part III para 3 : "this is within the 'normal' range of domestic gas explosions."
5.05 Para 159 of the Ronan Point report states explosions from "butane gas cylinders" (LPG) could cause explosions which might result in collapse. Para 173 suggests regulations on the storing of butane gas cylinders with reference to flats, be revised. Page 63, para 22 recommends regulations be reviewed.
5.06 In the Guardian 9 November 1968 Dr S.C.C.Bate head of Structural Engineering Division of the Building Research Station stated that explosion of bottled gas could cause progressive collapse, also paraffin explosions could cause progressive collapse.
5.07 The Liquified Petroleum Gas Industry Technical Association publish a code, CP 7, chapter 2 para 211 states: "It is preferable that all LPG is stored in the open air."
5.08 The report of H.M.Inspector of Explosives HMSO 31 Dec 1974 states on LPG: "There is no statutory requirement that an accident involving LPG be reported to us. Those accidents noted in Appendix J are those that happen to have been reported voluntarily. It is important to realise that the number of these reported incidents gives no indication of the extent of the danger caused by incidents involving LPG storage, use and conveyance. The incidents reported are however typical of many others".
"The energy locked in such a cylinder is equivalent to that of several pounds of explosives, and treatment such as heating it on a bonfire or even opening it in such a way that it is heated by the ignition of a pool of liquid ejected from it, can release this energy in a catastrophic way."
"The conclusion drawn from these accidents are...it is extremely dangerous to store or handle LPG in an enclosed space in circumstances in which a leak is forseeable, and that the making of any connection to a cylinder should be carried out in the open air." (p 20)
5.09 Tests at the Fire Research Station begun in 1973 on portable LPG heaters were extended to show the effects of a domestic fire on these heaters; a film was made. Findings:
a) In a domestic fire there was very high incidence of explosion within 20 minutes from the start of the fire with a full butane cylinder.
b) With a propane cylinder the explosion time was cut by 40%, to 12 minutes , and there is even greater risk of explosion.
c) "If following a domestic fire, a cylinder of LPG explodes, the original level of hazard is greatly increased, due to breakdown of natural fire barriers and injury from flying debris." (p 44).
5.10 Statistics of LPG Explosions and Accidents. From the Report of HM Explosions 1974, Appendix J, p 40 there were 8 reported explosions. For example in 1973 a fire in a hot dog stand caused an explosion of LPG. 1 person died and 19 were injured. On 11.1.74 a leak from an LPG heater in a shop ignited from a paraffin stove, the resulting explosion injured 2 people in the shop and 2 passers by.
Leeds Calor Gas, said there were six incidents in about 100,000 installations in the region. The Fire Research Station have the reports of official statistics. On checking with them a week ago we found Mr Slack had not consulted them.
The Home Office are currently preparing regulations on the use of Calor Gas (LPG). Tests at the Fire Research Station on a domestic fire acting on LPG heaters led to a film being made of the effects. We recommend that the Housing Services Committee see this film.
Mr Slack would not seem to be aware of these facts, and we are surprised. The full reports on LPG Explosions are covered by the official secrets act, and although not available to us they are to Mr Slack. As stated in para 5.03 we found a tenant with a 32 lb calor gas cylinder, and in another flat we found a 10 lb cylinder supplied by the Social Services Department. The lamp supplied had no on/off switch fitted to it. The only way to control this was by turning on the cylinder knob. This equipment had been there for a year.
5.11 Venting of explosions. We refer you to the Ronan Point Report, p 37, para 118. "The flank walls to the living room and bedroom however blew out from the side of the building". The explosion did not vent through the windows as Mr Slack hopes a calor gas explosion would do at Hunslet Grange. We also refer you to para 5.09 of our present report.
6.00 Conclusions. Calor gas explosions are equally, if not more likely than towns Gas explosions. Such an explosion following a leak or a fire is likely to be more powerful than that which caused the collapse at Ronan Point. It is doubtful if such an explosion would vent through windows.
7.00 Recommendations.
We recommend all calor gas is taken out of Hunslet Grange as Towns Gas has been. This is a national problem and we have written to the Minister of State for Energy - 8/7/76.
Joint report of Sam Webb, Dip Arch Hons RIBA and Dr Charles Wakstein BS.MA.PhD.
(tel Chartham 296) (tel Leeds 445579)
15th July 1976.