Sam Webb, Report on the overall structural conditions at Montieth Estate

ARCHIVE DOCUMENT
24 February 1984
Start of document

Report on the overall structural conditions at Montieth Estate,
Old Ford Road, Bow E.3 in the London Borough of Tower Hamlets.

1.00 Montieth Estate is a mixed development estate of High Rise
Blocks and four storey maisonette Blocks with access balconies.

1.01 The flats are system built of large loadbearing concrete panels.
The system used is Bison Wallframe for the maisonettes and
Bison High Wallframe for the tower blocks.

1.02 The Estate would have been constructed under the London
Building Acts 1930-39 and the constructional Bylaws of the
Greater London Council. These ane enforced by the District
Surveyor for the area.

2.00 Construction of the tower blocks Clare House and Antrim House
consists of a series of cross walls carrying vertical and
imposed loads to the foundations. Floors rest on the walls
by means of projecting cams. Looped reinforcement protrudes
from the edges of the floor slab and is engaged by dowels in
the wall.

2.01 Stability against wind loading is provided by the cross walls
in the short direction.

2.02 Stability against wind loading is provided longitudinally by
means of two parallel spine walls running along both sides
of the access corridor.

2.03 These walls are braced at right angles by the stair and lift
shafts.

2.04 In a high wind a tall building such as Clare House or Antrim
House will sway. The amount of sway will depend on the height,
plan form and construction of the block.

2.05 An indication of the amount of sway of a similarly constructed
building was given by Sir Alfred Pugsley O.B.E., F.R.S., M.I.C.E.,
MISTRUC E., the Engineer Member of the Ronan Point Tribunal.
He stated that in a 60mph wind that Ronan Point would sway 9"
(225mm).

2.06 Ronan Point is a 22 storey I.B. System Tower Block in the
Taylor Woodrow Anglian/Larsen and Neilsen System. Clare
House and Antrim House are 21 storey I.B. System Tower Blocks
in the Bison High Wall Frame System. The structural principles
of both systems are virtually the same apart from minor details.
Ronan Point did not have looped reinforcement as described in
para. 2.00.

2.07 If there were no spine walls in Antrim and Clare Houses
then all resistance to longitudinal overturning caused
by wind would have to be resisted by the floor to wall
joints of the cross walls.

2.08 Some Bison Flats were built in this way without spine walls.
These were 20 storey tower blocks at Pollockshaws in Glasgow,
built by Concrete (Scotland) Ltd. They were built for the
Corporation of Glasgow some 22 years ago. In these blocks
all the moments from wind loading are taken by the joints
between walls and floors.

3.00 This section deals with the conditions found at Montieth
Estate on Friday 24th February 1984.

3.01 The conditions in Flat 135 Donegal House are described in
a separate report.

3.02 Rain penetration through the gable end wall of this flat will
cause deterioration of the structure, and the structural
bearing of the floor slab. This could be exacerbated if
calcium chloride is present in the concrete mix.

3.03 Inspection around the base of Antrim House revealed a considerable
number of pieces of concrete which had fallen or been knocked
from the panels. There were also pieces of mosaic which had
fallen from the balcony fronts.

3.04 These pieces of concrete had come off the edges and corners
of the concrete panels. These are 8'0" square (2.400mm x
2.400mm). They varied from a long piece 12" (300mm) to
pieces 3" - 4" (75 - 100mm) cube. They weigh several pounds
each.

3.05 Inspection of this concrete reveals surface crazing and cracking
with fissures in the concrete itself. Concrete of this age
should not manifest such defects.

3.06 A logical conclusion to this cracking is that this concrete
contains calcium chloride.

3.07 Calcium chloride was added to concrete to speed up the set.
This enabled faster demoulding and working in low temperatures.

3.08 The effect of calcium chloride in reinforced concrete is to
reduce the bond strength of the reinforcing bars. The bars
will "pull out" or slide particularly in cantilevers, eventually
leading to collapse. It also causes the concrete to crack.

3.09 A factor that is of concern is that the presence of chlorides
could lead to a break down in the bond between the "decorative"
external panel and the wall ties which hold these on the
building. A number of these panels have fallen off Bison
Wall Frame blocks. One fell off a block in Woodside Glasgow
as recently as Friday 16th March 1984.

3.10 These 8'0" square decorative panels weigh 1 ton, they have
slipped or fallen off Bison blocks in:

Pollockshaws July 1982
Chelmsley Wood Birmingham July 1979
West St. Oldham 1973

details from World in Action Report Mon. June 20 1983.

3.11 In March 1984 the Association of Metropolitan Authorities
published "Defects in Housing 1960s - 1970s".

3.12 Pages 39 and 40 paras. 4.6 and 4.7 deal with calcium chloride.

3.13 Pages 45 and 46 paras. 5.7 - 5.10 deal specifically with
Bison and with calcium chloride.

3.14 The AMA Report states page 39:

"A separate, but related problem has been the use of calcium
chloride, which was widely used to accelerate concrete setting
times up to the mid 1970s. Deterioration is precipitated by
the weather. Both problems result in the reduction of
alkalinity of the concrete and weaken weather resistance.
However spalling concrete due to lack of cover to reinforcement
and concrete povority may be localised (although often
widespread in any structure) whereas the use of calcium chloride
produces a chemical change throughout the exposed concrete areas.
This is difficult if not impossible to arrest.

"Localised damage is itself expensive and difficult to treat;
calcium chloride problems threaten the whole structure and are
far more difficult and complex."

3.15 As previously stated the spine walls carry the longitudinal
wind loads.

3.16 On the twentieth floor of Clare House in flat 122, the internal
wall is formed by the lift shaft wall. This is parallel to the
spine wall.

3.17 The tenant, Mr. Fletcher, told me that the wall had three
diagonal cracks running from floor to ceiling.

3.18 Mr. Fletcher had filled these cracks with Polyfiller and papered
the wall. It was possible to feel the cracks under the paper.
The flat was extremely well looked after.

3.19 Mr. Fletcher said he had reported these cracks to the
Council but that no action had been taken.

3.20 Whether the Council official realised the significance is
difficult to say.

3.21 These cracks appear to be caused by excessive wind loading
which has caused this wall to fail in shear, hence the
diagonal cracks.

3.22 It should be a simple matter to see if these cracks go
through the wall by lowering the lift to the 19th floor
and making an inspection of the other side of this wall
inside the lift shaft.

3.23 It may be that these cracks are 'one off' cracks not found
in any other flat. Flat 122 was the only flat inspected
in the block. Mr. Fletcher was not told of the possible
significance of these diagonal cracks, and there is no
reason to worry him or his wife.

4.00 Recommendations.

4.01 An inspection of the wall to Mr. Fletcher's flat should be
made both inside his flat and inside the lift.

4.02 This spine wall should be checked on other floors, in the
fire stairs and in the refuse room on both sides of the
access corridor to ascertain if it is cracked on other floors.

4.03 The structural stability of Bison Flats has been called into
question by the Minister of Housing Ian Gow M.P. The London
Borough of Tower Hamlets should satisfy themselves over this
if they are not officially aware of the diagonal cracks in the
wall of the living room in flat 122 Clare House. The Council
should check for the presence of chloride in the structural walls.

4.04 The Council should also check the stability of the gable end
wall in Flat 135 Donegal House particularly in the light of
reports made on Bison flats in Hillingdon and Hounslow.

4.05 Copies of this Report are being sent to:
Tower Hamlets Tenants Federation
Oxford House
Derbyshire Street, E.2
The Chairman of the Housing Committee
The London Borough of Tower Hamlets
The District Surveyor
The London Borough of Tower Hamlets

4.06 This Report has been made at the request of the Tower Hamlets
Tenants Federation.

Sam Webb RIBA
The Senior Lecturer in Advanced Technology
The School of Architecture
Canterbury College of Art
New Dover Road
CT1 3AN
0227 69371

WESA_5_5_02p1
1 of 6