Sam Webb, Morris Walk, Greenwich, Report to Tenants

Sam Webb ARCHITECT RIBA
Walnut Tree Cottage, 68 Shalmsford Street, Chartham, Canterbury, Kent CT4 7RH.
Telephone: Canterbury (0227) 738296.
- 5 AUG 1988
[stamp: Hunt, Thompson Associates]
REPORT TO THE TENANTS
OF THE
MORRIS WALK ESTATE
IN THE
LONDON BOROUGH OF GREENWICH
MAY 1985
May 1985 Sam Webb RIBA
SAM WEBB Architect
WALNUT TREE COTTAGE
68 SHALMSFORD STREET
CHARTHAM
CANTERBURY
KENT CT4 7RH
[page 2]
Sam Webb ARCHITECT RIBA
Walnut Tree Cottage, 68 Shalmsford Street, Chartham, Canterbury, Kent CT4 7RH.
Telephone: Canterbury (0227) 738296.
" It is neither prudent nor wise to
strengthen large panel construction
of whatever system to 5 p.s.i. whether
or not gas is used."
[page 3 - Introduction]
Sam Webb ARCHITECT RIBA
Walnut Tree Cottage, 68 Shalmsford Street, Chartham, Canterbury, Kent CT4 7RH.
Telephone: Canterbury (0227) 738296.
1.00 Introduction
In November 1984 I was approached by the London Borough of Greenwich and asked if I would aid the tenants in choosing an Engineer, prepare a report on the structural condition of Morris Walk Estate, and advise the Engineer about Taylor Woodrow Anglian Construction with regard to the work I had done on Ronan Point so that he could prepare a report.
1.01 In November 1983 I carried out surveys in flats in Ronan Point and other blocks on the Freemason's Road Estate in Newham for the Newham Tower Blocks Tenants Campaign and in the Aintree Estate Fulham. This is a 14 storey TWA/LN Estate of two tower blocks with virtually identical construction to Morris Walk. It was built by the GLC. In May 1984 I was invited to Haringey to look at Broadwater Farm as a result of my survey Building Design Partnership were called in.
1.02 As a result of a report on Flat 26 Ronan Point and a survey I carried out in March 1984 The London Borough of Newham evacuated Ronan Point so that independent tests by BDP could be carried out firstly into the difficiencies in fire compartmentation and then into the structural problems I had found. At my request Thomas Akroyd was appointed to look at further aspects of Ronan Point.
1.03 In July 1984 a fire test was held in Ronan Point by the Building Research Establishment and the Fire Research Station. This test was terminated by the Engineers in charge;because of the risk to the structure,after only 12 mins. It had been scheduled to run for 30 minutes.
1.04 In September 1984 the loadbearing flank wall and floor joint of Ronan Point was opened up. It was not in accordance with the drawings. The insitu concrete had not been compacted, nor had the dry pack under the walls. This caused voids.
1.05 Following this discovery and further reports from B.D.P., Thomas Akroyd and myself, a full meeting of Newham Council voted to demolish Ronan Point and five similar blocks.
1.06 A series of cuestions were then asked in Parliament by the MP for Newham South, Nigel Spearing MP. He asked on October 23 1983 what action the Government were taking into other large panel systems buildings of the Taylor Woodrow Anglian type, and that I be given permission to consult the official files of the Ronan Point Inquiry bearing in mind the inability of the D.O.E. to find altered paragraphs. On a visit to the files Nigel Spearing and I located the deleted passages.
1.07 The Minister of Housing & Construction Ian Gow MP instructed the BRE to investigate as a matter of urgency Ronan Point and other TWA/LN Buildings, and allowed me to consult the official files. These files have reference to Morris Walk and other large panel construction. There is also concern about the use of L.P.G.
[page 4]
Sam Webb ARCHITECT RIBA
Walnut Tree Cottage, 68 Shalmsford Street, Chartham, Canterbury, Kent CT4 7RH.
Telephone: Canterbury (0227) 738296.
1.08 Much of this was reported in the Times by Charles Knevitt and by various T.V. and radio programmes. This led the tenants to contact Greenwich and ask if I could help them.
1.09 At 5pm on Friday 10th May 1985 the BRE produced their report which stated that parts of the load bearing H.2 joint"had an unacceptable margin of safety." I had reported that fact to Newham's Chairman of Housing Mr. Fred Jones in April 1984.
1.10 Some of my qualifications are
Diploma in Architecture with Honours (Northern
Polytechnic 1962).
Associate of the Royal Institute of British Architects 1965
Member of the RIBA Council 1973-76 and 1978-81
Member of the Building Control Panel of the RIBA 1978-80
This panel is concerned with building codes, regulations
and the construction of buildings.
Member of the RIBA Education Committee 1979-81
I am the Senior Lecturer in Advanced Technology in
The School of Architecture Canterbury College of Art.
In 1968 George Fairweather FRIBA of Fairweather & Webb Architects
28/30 Wigmore Street W.1. gave evidence at the Ronan Point Public
Inquiry. I helped in preparation of his evidence. Among other
things he was Chairman of BSCP CP3 "Fire precautions in flats and
maisonettes over 80'0" in height." He chaired the later Code
which now applies to flats and maisonettes over 3 storeys.
From 1961 to 1965 I helped George Fairweather in his advice to
East Ham V. Bernard Sunley.On Fairweather's advice this case
was taken to the House of Lords by East Ham. They won the case.
I have written many articles in technical journals on TWA/LN and
Ronan Point including articles in the RIBA journal on the
implications of the High Court Judgement in December 1979
"The London Borough of Newham
v
Taylor Woodrow-Anglian Ltd."
Many authors have referred to my research into TWA/LN and Ronan
Point including Barry Russell in his book "Building Systems,
Industrialisation and Architecture" published by Wiley 1981.
This book is the definitive edition on the subject.
I attach the relevant passages from Hansard and the altered
passage from the Draft Report of 1 October 1968.
[Hansard extract - Written Answers 23 OCTOBER 1984]
553 Written Answers 23 OCTOBER 1984 Written Answers 554
[left column]
my statement of 6 September, there are compelling reasons why this cannot be done. I did say that the Merseyside Development Corporation was looking into ways of making more of the site open to the public next year in addition to those substantial parts which have always been intended to be retained as a permanent facility. The MDC has since confirmed that many of these superb facilities will be open to the public next year.
South Yorkshire (Rates)
Mr. Mason asked the Secretary of State for the Environment how many letters he has received from people residing in the Barnsley, Central constituency complaining about the levels of South Yorkshire county council rates.
Mr. Waldegrave: None since the White Paper on rates was published in August 1983.
Wembley (Amusement Centres)
Mr. Pavitt asked the Secretary of State for the Environment why he overturned the unanimous decision of the borough of Brent to refuse planning permission for proposed amusement centres and a gaming licence for premises in Wembley high road.
Mr. Macfarlane: This planning appeal was determined not by my right hon. Friend, but by an inspector appointed by him. In allowing the appeal the inspector granted conditional planning permission only. Full reasons for his decision are set out in his letter dated 29 June 1984. I am arranging for a copy of this letter to be sent to the hon. Member.
Application for a gaming licence is subject to the Gaming Act 1968 and would be a matter for my right hon. and learned Friend the Home Secretary.
Ronan Point
[X mark] Mr. Spearing asked the Secretary of State for the Environment what action he has taken in respect of the representations he has received concerning changes to the draft of the Departmental inquiry report on the collapse of Ronan Point; and if he will make a statement.
Mr. Gow: The following is the text of a letter which I sent yesterday to the hon. Member:
RONAN POINT—Inquiry Report
You have put down a Parliamentary Question for answer on Tuesday 23 October to ask what action the Secretary of State "has taken in respect of the representations he has received concerning changes to the draft of the Departmental Inquiry Report on the collapse of Ronan Point".
On 12 October you wrote to the Secretary of State to ask him to look into reports in The Times which referred to this matter and to obtain the reaction and recollections of the members of the Tribunal of Inquiry. I understand that separately Mr. Sam Webb, acting as your research assistant, has asked on your behalf that he be given access to the working documents and other papers of the Tribunal. He has explained that he had access to these papers for some 3½ weeks in 1970.
I am writing to you straightaway and propose to reproduce the text of this letter in answering your question.
The Tribunal was appointed by the then Minister of Housing and Local Government, the right hon. Anthony Greenwood, MP by instruments dated 17 May and 21 May 1968 to hold a public inquiry under section 318 of the Public Health Act 1936 and section 290 of the Local
[right column]
Government Act 1933 with the terms of reference set out in paragraph 1 of the Tribunal's report. In accordance with the usual practice the Tribunal was assisted by a Secretary and other staff provided by the Ministry of Housing and Local Government.
The Tribunal concluded its oral hearings on 2 August 1968; its report was signed on 14 October 1968 and was transmitted to the Minister with a letter from the Chairman, Mr. Hugh Griffiths, QC dated 14 October 1968.
The papers of the Tribunal and the related departmental files contain no evidence that the text signed by the members of the Tribunal and its secretary, and for which the members alone were responsible, was altered between its signature, receipt by the Minister, and printing. In early working drafts of the chapter concerned there is evidence of changes on the lines suggested in The Times article but although some amendments are in manuscript as described in The Times we have been unable to find any sheet containing in The Times we have been able to find no sheet containing the words "However in popular terms to make walls strong enough to resist 60 lbs sq. ft. is only to make them about as strong as the glass in a good window" deleted in a broad nibbed pen in purple ink. [*asterisk mark in margin]
But such changes were matters for the members of the Tribunal. It would be normal for a report of this length and complexity to pass through a number of drafts containing significant variations, and I do not think that it would be fair to members of the Tribunal, or proper, to attach any particular importance to forms of words which they decided during the drafting process not to include in their report to the Minister. In any event, deletions and changes made at that stage cannot be the responsibility of a civil servant as alleged in The Times.
The papers of the Tribunal form part of the papers of the Department and are public records for the purposes of the Public Records Acts. They have been recovered from storage in order to consider the matters raised in your Question and letter, and are now being assembled in proper order. It is unusual for access to be given to public records well within the 30-year rule, but, as there has been earlier public access to papers of the Tribunal, I have agreed that further access should be given.
As a matter of good practice in giving access to records, it is essential that they should be properly ordered, secured and catalogued. This will be done as soon as possible. I will let you know when the papers are ready for public access.
[X mark] Mr. Spearing asked the Secretary of State for the Environment what reports he has received from the London borough of Newham concerning the condition of Ronan Point and similar tower blocks built with the Taylor-Woodrow-Anglian system; and what action he is taking in respect of such blocks built in Newham and elsewhere.
Mr. Gow: 1. In order to understand the implications of the reports received by the London Borough of Newham for Ronan Point and other large-panel blocks of flats it is necessary to take account of the events of 1968 and subsequent action by the Government and local authorities.
Background: Events in 1968 and immediately thereafter
2. In 1968 Ronan Point, a tower block built in the Taylor-Woodrow-Anglian system, suffered a partial collapse. The subsequent tribunal of inquiry in its report, "Collapse of Flats at Ronan Point, Canning Town" (HMSO 1968), found that an explosion of town gas blew out concrete panels forming part of the load-bearing flank wall of one flat. As a result, there was progressive collapse of the south-east corner of the block.
3. The tribunal made a series of recommendations affecting system-built blocks of flats over six storeys in height. These included measures to strengthen Ronan Point itself; measures to appraise and, if needed, to
[* doc 387-1. 10. 68 handwritten note in margin]
[page - Hansard continued, 557]
557 Written Answers 23 OCTOBER [1984]
I have considered the advice so far available to me and have decided to take the action set out in the following paragraphs.
16. First, I do not consider that the findings at Ronan Point to date need cause other owners of blocks constructed in the same or other large panel systems to contemplate immediate rehousing of residents or that they justify conclusions on the long term future of such blocks. Each authority must of course make its own managment decision in the light of all the relevant circumstances.
17. Second, authorities should consider urgently practical steps to prevent the use and storage of LPG cylinders or other explosive materials in:
(a) all blocks ove six storeys in height built of large pre-cast concrete panels to form load-bearing walls or floors, or both, not designed or strengthened to resist a standard static pressure of 5 psi (mains gas should have been disconnected from such buildings);
(b) any other blocks, whether of flats or houses, which do not satisfy the requirements of section D17 of the Building Regulations, which applies to buildings having five or more storeys (including basement storeys, if any).
The advice on blocks over six storeys essentially reiterates the advice given in the inquiry report, MHLG circular 62/68, the Home Office's Fire Prevention Guide No. 4, "The safe use and storage of liquefied petroleum gas in residential premises" (HMSO 1976) and the second annual report of the Engineering Institution's Standing Committee on Structural Safety (Chairman, Lord Penney) in 1978.
18. The advice on other blocks is a reflection of the fact that progressive collapse could occur in certain buildings of less than seven storeys. It should be noted that in 1978 the principal suppliers of LPG advised their agents not to make cylinders of LPG available to customers in blocks of flats and maisonettes of more than four storeys whatever their form of construction. The Department has evidence that despite these warnings the use of LPG heaters by tenants is increasing.
19. Third, the BRE is devoting and will devote whatever resources are necessary to investigate as a matter of urgency the problems highlighted at Ronan Point and to provide advice on structural appraisal and remedial measures as necessary. This will involve a significant input of resources by the BRE into the problems of large panel systems of construction. The Department intends to discuss the formulation of this programme of work with the local authority associations as soon as the immediate work by BRE on Ronan Point makes it possible.
20. Further guidance to owners of Taylor-Woodrow-Anglian buildings will be issued in the light of BRE's evaluation of the evidence.
21. The Department will be writing this week to inform local authorities of the action which we consider owners of dwellings of large-panel construction ought to take now, to give further details of the action which might be taken now, to give further details of the action which might be taken on LPG, and to ask for any technical reports and information which authorities may have on large-panel buildings in their ownership. A copy of the Department's letter will be placed in the Library.
[handwritten annotation page]
"It would seem to us very
unfortunate if in a wind
liable to break many glass
windows-(those at Ronan
Point have been found to
break at 16pt2.) the
inhabitants of Ronan Pt
should also have to start
worrying about its
structural stability"
Written by Sir Alfred Pugsley →
All the deletions are by
the Chairman of the Tribunal.
This is the marginalised note which has been crossed out.
The page opposite is p 18 (doc 387) comes from the draft chapter on Structure written by Sir Alfred Pugsley.
The comments in the margin (above) and the one at the bottom were also written by him.
The deletions are by someone else.
It would seem obvious that Pugsley was not happy with the deletions otherwise there was no need to write the other comment (which is probably more frightening) in the margin.
The para at the bottom refers to collapse in a fire.
[annotated page: DRAFT OF THE FINAL RONAN PT REPORT sent to the Minister. 387.]
DRAFT OF THE FINAL RONAN PT REPORT
sent to the Minister.
387.
[illegible] 1/10/68
- 18 -
'C' →
18. The chance of such a wind occurring in a given year is of course only 1 in 60, and to allow for it may be thought too cautious in action, but it should be remembered that to make the walls and their joints capable of withstanding pressures, for example, of 45 lb./ft.2 would be only to make [highlighted text] them about as strong as the glass in ordinary windows. [end highlight]
To think these results are such that the external walls of Ronan Point should be strengthened against suction as soon as practicable, aiming to make them withstand safely suctions up to 65 lb./ft.2. We think also that the general strength of the tower in bending in high winds should be examined in the light of the results quoted in paragraph 17 above with a view to strengthening the load bearing walls in the critical regions. [struck through: We would suggest, as a first step, consideration of the practicability of increasing the efficiency of the H.2 joints in compression.]
147. For urgent consideration also is the question of whether special wind tunnel tests should be conducted on a model of Ronan Point and on a model of the group of nine such buildings planned for the Clover Ness area. We suggest that this matter be put to the Aerodynamics Division of the National Physical Laboratory. [handwritten: (arise). Alms]
18.8. Two further points [handwritten text illegible] The first, and the most important, relates to the possible effects of a fire in one of the flats at Ronan Point. The prob[able] performance of individual components of the building, such as wall and floor slabs, [text continues with handwritten annotations] discussed with the Fire Research Office at the time the building was designed and [illegible] considered satisfactory. But the point now raised concerns the effect on the [handwritten: ceilings or] flank walls of the expansion of a [struck through: ceiling or] door due to the very high temperatures that can arise even in a domestic fire. It is estimated that this [highlighted text] could push an H.2 joint outwards by as much as 0 inches, and not endanger the stability of the flank wall as well as make it possible for a floor panel, [end highlight]
/on its
[marginal handwritten annotations illegible]
[letter: 2 Crown Office Row]
2, Crown Office Row,
Temple, E. C. 4.
01-353 9337.
Monday 14th Oct 68
Dear [illegible],
I am sorry that our report has taken a few weeks longer than I had anticipated when I wrote to you on the 6th August. But the tests and investigations put in hand as a result of the evidence at the Inquiry took rather longer than I had anticipated.
[continued]
I hope you will think we were right to deal with the question of wind loading although to do so is obviously stretching our terms of reference. But it seemed to us a matter of such general importance that the engineering profession and the building industry should be alerted to it; and although we have deliberately not referred to it in the report, to avoid undue public anxiety, I have no doubt you know that a system built block in Glasgow has already suffered serious wind damage. Yours sincerely
[signed] Hugh [illegible]
[letter: London Borough of Camden]
London Borough of Camden The Town Hall
Euston Road
Councillor Geoffrey Finsberg, M.B.E., J.P., London N W 1
Leader of the Council Telephone: 01-837 7070
[handwritten: S. Webb copy. S.H.]
[handwritten: Spoken to Mr Finsberg]
13th September, 1968.
S.A.G. Cook Esq., A.R.I.B.A.,
Borough Architect,
The Old Town Hall,
High Holborn, W.C.1.
Dear Mr. Cook,
Many thanks for sending me the photostat letter which one of your staff has written on the subject of high flats. It strikes me as being extremely important and I wonder what reaction has been, or is likely to be, received from the Ministry.
Yours sincerely,
[signed]
GEOFFREY FINSBERG
BOROUGH ARCHITECT
CAMDEN
13 SEP 1968
GROUP:
FILE No.
[letter: Ministry of Housing]
[crest of Ministry of Housing and Local Government]
WHITEHALL,
LONDON, S.W.I.
30 April 1970
Dear Colleague,
/ Thank you for letting me see this letter from Mr Sam Webb of No 9 St Annes Close, Highgate West Hill about structural stability in system-built flats and in particular the question of steel angles used in strengthening work. I appreciate the points he is making; however there are one or two comments I should like to make.
It must be for the local authorities (or the District Surveyors, so far as they are concerned, in Inner London) to apply the regulations and byelaws, and any questions of interpretation would normally be for the Courts. My function is mainly to make or amend the regulations, and not to deal with particular schemes except where special questions, eg of relaxation, are referred to me.
So it is really not possible for me to inquire into and pass judgment on what the Greater London Council or other authorities do in particular cases under the byelaws or regulations. They have, as you know, their own highly qualified professional staff and they have had available to them also advice from both the National Building Agency and the panel of experts from the architectural and structural engineering professions, which was set up after the Tribunal reported.
Mr Webb was quite right to try and get his views ventilated in professional circles and especially in connexion with the appropriate Codes of Practice - this is where a technical matter of this kind can best be pursued.
In so far as Mr Webb is saying that there is a loophole in the Building Regulations, I am always prepared to consider amending them (after the appropriate statutory consultations) but there must be a certain weight of informed opinion behind any such move, and that is why
[continued]
I say again that the right way for Mr Webb to pursue the matter he is now raising is in the profession and amongst those who are discussing Codes of Practice.
Yours sincerely
[signed] Antony [illegible]
Arthur Lewis Esq MP
[Sam Webb report continued - section 2.00]
Sam Webb ARCHITECT RIBA
Walnut Tree Cottage, 68 Shalmsford Street, Chartham, Canterbury, Kent CT4 7RH.
Telephone: Canterbury (0227) 738296.
2.00 Morris Walk and Ronan Point.
2.01 The Morris Walk Estate was the first TWA/LN Estate built in this country for the then London County Council. Ten further estates were built in London for the LCC/GLC. Other TWA Estates are in Westminster, Haringey and Newham.
2.02 The tallest TWA buildings in London, nine in total are in the Ronan Point series in Newham, of 22 storeys, followed by Haringey with two blocks of 17 storeys at Broadwater Farm and 14 storey blocks in the Morris Walk Series at Aintree Estate and Barley Mow.
2.03 Morris Walk itself is ten storeys in height.
2.04 On 3 July 1968 Eric Bunn the Structural Engineer to the Greater London Council had a meeting with Mr. Humphreys acting for the Litigation Division which instructed the Treasury Solicitor in the Ronan Point Inquiry. A note in the files (para. 1.07) stated:
" Mr. Bunn said that inquiries which he would have to make
before making another statement may well cause alarm since the
Larsen & Nielsen system introduced by T.W.A. had undoubtedly
been modified as thh years went by and the earlier buildings
were not as stable as the later ones."
2.05 Mr. Bunn did not make another statement but in evidence had this to say:
"I have read the proof of the statement by Mr. Victor Watson
(of Phillips Consultants) and examined the drawings submitted
concerning the construction of Ronan Point, and I am able to
confirm that in essence the system of construction, the method
of erection anddetails of the various joints are the same or
comparable to those developed and used during the erection of
the Morris Walk Series.
" I am unable to comment on the overall stability of Ronan Point
block having not seen the calculations etc., but as stated above,
the plan form is such that it should have an equal if not greater
factor of safety than that provided in the Morris Walk Series."
Friday July 12 1968 Evidence Day 8 page 7 at C and D.
2.06 The erection team at Ronan Point was part of the erection team from Morris Walk.
2.07 The plan of Morris Walk is different to Ronan Point and the height is 10 storeys against 22 or 24 if the two storey podium is counted.
2.08 The highest Larsen & Nielsen Buildings in Denmark are the 9 and 16 storey 'High Gladsaxe' flats outside Copenhagen. These flats have prestressed joints and walls. Danish Regulations would not appear to allow the form of construction used in this country because of the problem of bending moments in the joints.
2.09 There is a paper on this in "Housing from the Factory" page 143 by the design engineer for Larsen & Nielsen.
2.10 The original Larsen & Nielsen H.2 joint is shown in the diagram. This has an upstand against which the drypack can be rammed and seems a much better joint for a lowrise building from this point of view.
[HAND-DRAWN ENGINEERING DRAWING]
[Title: MORRIS WALK PLAN. 3/1 BED AT TOP 2/2 BED BELOW]
[Title: ORIGINAL LARSEN E NIELSEN SYSTEM JOINT FLANK WALL TO FLOOR JOINT LOADBEARING H2 SAM WEBB RIBA MARCH 1985]
[HAND-DRAWN ENGINEERING DRAWING]
[Title: H 2 MORRIS WALK SAM WEBB RIBA MARCH 1985]
[Title: H2 JOINT MORRIS WALK]
[HAND-DRAWN ENGINEERING DRAWING]
[Title: WINEGLASS FLOOR JOINT MORRIS WALK]
[Title: V13 FLANK WALL]
[HAND-DRAWN ENGINEERING DRAWING]
[Title: H 4 CROSS WALL SECTION]
[Title: PLAN CROSS WALL & EXTERNAL NON LOADBEARING FACE WALL (T)]
[HAND-DRAWN ENGINEERING DRAWING]
[Title: CORNER X]
[Title: STAIRCASE CORNER Y]
[HAND-DRAWN ENGINEERING DRAWING]
[Title: H 1 JOINT MORRIS WALK]
[HAND-DRAWN ENGINEERING DRAWING]
[Title: STAIRCASE BEARING NIB (A)]
[Title: STAIRCASE (Z)]
[Sam Webb report continued - section 3.00]
Sam Webb ARCHITECT RIBA
Walnut Tree Cottage, 68 Shalmsford Street, Chartham, Canterbury, Kent CT4 7RH.
Telephone: Canterbury (0227) 738296.
3.00 Documents, drawings consulted and research.
3.01 Access has been granted me by the Minister of Housing and Construction Ian Gow MP at the request of Nigel Spearing MP to consult the Ronan Point Public Inquiry Files.
3.02 In 1968 these files and working papers were filed in "6 files and 28 Plan Covers". The plan covers were numbered in sequence 1 - 28, and "plan covers 14 - 27 (inclusive) are at this time, missing."
3.03 The Minister stated in his reply to Nigel Spearing MP that the documents would be, "properly ordered, secured and catalogued." This has been done and all the files have been renumbered because when they were got out of the central file they were found "to be in a disordered state."
3.04 I estimate that half the files I originally consulted in 1970 are now missing and I have had an informal request for some of my files so that the gaps can be filled.
3.05 These files contain references to Morris Walk and the Morris Walk Series.These have been made available to Fothergill & Co.
3.06 I have two copies of the Transcript of the Public Inquiry into Ronan Point. One of these sets has been loaned to Fothergill & Co.
3.07 All of my many copies of reports and drawings on the structure of TWA/LN have been made available to Fothergill & Co.
3.08 A set of drawings of all the panels has been consulted together with a set of Larsen & Nielsen joint details. I am not sure if these were the actual joints built. I have found that other Boroughs like Hackney do not have the joint drawings of their Gascoyne Estate which is identical to Morris Walk.
3.09 In view of the importance of this work visits have been made to all the Morris Walk Series Estates to identify any common deficiencies and changes in construction since Morris Walk was built.
3.10 Discussions have been held with Engineers and Architects concerned with TWA LN Estates. (I have obtained reports from the GLC).
3.11 All of my contacts, including other engineers and architects involved in investigations have been made available to Fothergill & Co.
3.12 Whatever the outcome of these inquiries it is important that the Tenants of Morris Walk are satisfied that their interests and safety are fully considered.
4.00 Workmanship
4.01 The quality of the workmanship in the structural joints of Morris Walk is crucial to the stability of the building and its structural integrity.
4.02 During the investigations at Ronan Point and other blocks on the Freemason's Road Estate which followed as a result of the original investigations I carried out from November 1983 onwards a number of joints were exposed by Newham's Engineers, B.D.P., Thomas Ackroyd and the BRE.
4.03 In every report on Ronan Point either made verbally or written to the Council, the tenants or myself it was stated "that in all respects the drypack was good" or similar wording.
4.04 On 4th August at a Public meeting at Newham Town Hall it was stated that Ronan Point was "structurally sound", that "it had safely withstood all loads etc." ..
4.05 This was a view not shared by the tenants, the Chairman of Housing or myself.
4.06 In late August 1984 the Engineers were asked by the Tenants when they were going to open the H2 Flank Wall Joint.
4.07 On all occasions we had been told that the H2 joint was sound and there was no risk.
4.08 I had previously predicted certain cracking of the wall panels which could not be seen; unless the joint was opened up. This was made at a Public Meeting in October 1983, in reports to the Council, and in a paper to the Public Meeting on Ronan Point held at the City University in February 1969. This meeting was chaired by Sir Alfred Pugsley and was reported in the Journal of the Institution of Structural Engineers.
4.09 I was not satisfied with the answers that I received over the quality of workmanship in the H.2 joint either in 1969 or during the investigations in 1984. Neither were the tenants in 1984.
4.10 In September 1984 core samples were taken in the H.2 joints on the north loadbearing flank wall of Ronan Point.
4.11 Water poured through the joints as the cores were being cut indicating voids in the concrete. This has also happened in test core drilling in Morris Walk.
4.12 The joints were opened up and concrete was "significantly voided".
4.13 This means in layman's terms that it had holes in it. No stress can be transferred through these holes, therefore the stresses will be more concentrated in certain parts of the wall particularly around the lifting bolts and the bolts holding the angles to the floor/ceiling and walls. There is no reinforcement in the concrete to help transfer these stresses and cracks may well develop. These cracks will not necessarily show up on a radar survey.
4.14 After opening the joints and finding much of the drypack not there the Engineers then discovered that the floor slabs were resting on the angles. The angles were not designed to do this.
4.15 In a letter to me in 1970 Sir Hubert Bennett FRIBA Architect to the Council GLC stated that apart from explosions "the angles are unloaded at all times". To my query about fireproofing of these angles he stated that this was "considered an unnecessary expense."
4.16 It would now appear that the angles require fireproofing because the floors may be resting on them. I am not confident of the long term structural behaviour of this joint.
4.17 At this stage I am unable to give an assurance concerning the ability of the H.2 (loadbearing Flankwall, Floor Slab joint) to continue to serve the function for which it was designed.
4.18 Many of the designer's original assumptions about this joint have not been borne out in practice. Movement has occurred in relation to the wall floor angles and bolts in a number of TWA/LN Buildings throughout London. This has taken place in spite of assurances that it would not occur. There is no indication that it has stopped.
4.19 Such movement can be caused by the gradual squeezing of the drypack between the top and bottom of the wall slab. This has created stresses around the bolts which have caused the bolts to bend and the concrete to crack. I reported to Newham that this might have happened in Ronan Point as early as November 1983 in discussions I had with one of their senior engineers. It is also in my paper to the 1969 Meeting on Ronan Point, also in Building Design 17 Jan. 1973 p.14.
4.20 In September 1984 when the H.2 was opened these cracks were found.
4.21 There is another aspect of the H.2, H.4 and V.13 equivalent joints in Morris Walk. During my inspections of Ronan Point and the other 8 blocks I found evidence of water penetration into the structural joints.
4.22 This was pointed out to all parties concerned. The B.R.E. Report states para. 7.14.
" BDP report no rain penetration through cladding and one instance of leakage at roof level. Thomas Ackroyd made no comment, whilst Webb reports water penetration into the loadbearing structure especially the H.4 joint, and the roof. Such penetration could lead to long-term deterioration of structural joints" etc.
BRE Report "The Structure of Ronan Point and other Taylor Woodrow-Anglian Buildings" 10 May 1985.
4.23 In their conclusions para. 12.11 the BRE make a request for further investigations on the matter of rain penetration in TWA/LN buildings.
4.24 Until the BRE published their report on 10 May 1985 the only other report on rain penetration has been by myself so the weight of evidence would seem to have precluded its discussion by other engineers in the past.
4.25 During a recent visit to Morris Walk at which John Nind was present I pointed out the penetration of rain in one of the flats. This flat was being used by contractors as their site office (No.3 Lolland House), and the water has penetrated some way through the H.4 joint discolouring the decorations. This is in the W.C.
4.26 Rain water can penetrate through the vertical V.13 joint between adjacent wall panels, through voids in the H.2 Flank wall floor joint and into the cores of the floor slab. It can also penetrate through the H.1 face panel joints into the H.4 loadbearing cross wall joints.
4.27 While this may not be serious now, from a structural point of view over the long term this will cause deterioration of the load carrying capacity of the structure causing settlement and possible overstressing in parts.
4.28 On the evidence to date I consider that there are unresolved questions about the workmanship in the H.2 joint in Morris Walk. The BRE state
"The importance of the H.2 joint (in Ronan Point) merits consideration
in depth so as to explore the limits of uncertainty and to achieve
the best assurance of safety without undue conservatism. In the final
result it will be seen that, whatever the numbers say, the judgement
needed to interpret them is an important part of the process."
para. F.1 BRE Report 1985.
4.29 I understand that the SENSELB Committee: ('Senior Structural Engineers in the London Boroughs') are critical of the BRE Report and feel that the BRE should undertake further tests of critical joints including the H.2. A member of that committee has told me that if the BRE does not carry out these tests, then the committee will commission their own independent tests.
4.30 In the light of this my considered opinion is that these joints merit further investigation through opening up for inspection, before any final judgement can be made.
5.00 Structural Risk from Explosion.
5.01 Virtually every report that I have read on large panel construction states:
"It is worth stating by way of introduction to this chapter that these tower blocks have withstood all normally applied loads (Dead load, live loads and wind loads) in their 15 to 20 year life in a satisfactory fashion."
This is a dangerous fallacy.
5.02 It should not be supposed that, because buildings of a certain type have stood and not failed over a period of years, that this fact in itself is either:
a) A guarantee of their safety
b) The building has the normal factor of safety demanded
c) Any other building constructed on the same principles is safe.
5.03 The margin of safety in a complex structure like Morris Walk or Ronan Point is extremely difficult to assess so long as no failure occurs.
5.04 The primary function of the factor of safety in a structure is to provide a safeguard against the unexpected and unforeseeable.
5.05 This principle has long been interlinked with basic concepts of structural safety.
5.06 This philosophy on structure was stated at the Ronan Point Public Inquiry by a number of Engineers and an Architect.
5.07 One of those Engineers was
Frank M. Bowen M.I.C.E., M.I. Struc.E. of
Scott Wilson Kirkpatrick & Partners
Past President of the
Institution of Structural Engineers
and District Surveyors Examiner.
5.08 The Architect was
George Fairweather F.R.I.B.A. of
Fairweather & Webb Architects
The Chairman B.S.C.P. C.P.3 : Chap. IV (1962)
" Precautions against Fire, Part 1.
Fire precautions in flats and maisonettes
over 80'0" in height."
Member of the Tribunal of Appeal under The London Building Acts
and District Surveyor's Examiner.
5.09 In 1968 I helped George Fairweather FRIBA prepare his evidence for the Ronan Point Inquiry. He gave this on the Fourteenth Day, 24 July 1968.
5.10 In important respects Morris Estate and all of the Taylor Woodrow Anglian/Larsen Nielsen Buildings that I have personally inspected including ones built to the higher standard of 5 p.s.i. (34 KN m2) FAIL TO COMPLY WITH BSCP CP3.
5.11 In my opinion there is an unacceptable risk of collapse in Morris Walk in relation to:
a) the explosion of a cloud of calor gas,
propane gas or any form of liquified
petroleum gas in a room or rooms.
b) the explosion of petrol vapour or any volatile liquid
such as petrol, thinners etc.
c) the explosion of a calor or propane cylinder
whether full or not.
5.12 At the recent one day G.L.C. seminar on Feb. 21 1985 on TWA/LN construction, Dr. Menzies of the BRE stated in answer to a question from me that he thought that a TWA/LN building would not suffer structural failure if a propane or calor gas cylinder exploded either before, during or after a fire.
5.13 This is a view that I do not share and it would appear that the BRE and Dr. Menzies have changed their minds on this matter since the GLC Meeting.
5.14 But acceptance of this fact :by the B.R.E. has now led to yet another and possibly even more dangerous situation.
5.15 The recommendation of the Government and the BRE is that Councils must ban the use of calor gas cylinders in large panel construction over 6 storeys.
5.16 No indication is given on how this is to be done.
5.17 However if Councils cannot enforce this ban they must strengthen the buildings to resist 5 p.s.i. (34 KN m2) static pressure.
5.18 The explosive force from an explosion may be higher than 5 p.s.i.
5.19 No money is to be provided for this work.
5.20 After the Ibrox Football disaster in 1961 in which 66 people died, "The Safety in Sports Ground Act" was passed. It did not apply to third and fourth division grounds.
5.21 Within hours of the Bradford City Fire disaster last week the Home Secretary enforced the Act on third and fourth division clubs.
5.22 Are we to suffer great loss of life on a Council estate in this country before the Government makes adequate money available for safe efficient and economic heating?
5.23 There are widespread national implications in this matter of LPG portable cylinder heating which is crucial to the safety of the tenants.
5.24 From inquiries that I have made it would appear that heating multi storey cooking or lighting by Liquified Petroleum Gas (LPG) in buildings is banned in the following countries: France, Germany and Israel, if portable containers are used.
5.25 L.P.G. supply from cylinders properly installed by trained fitters is perfectly safe. In areas where there is no piped gas it is frequently used as a substitute. In all cases where the appliances served by LPG are fixed then all the cylinders must be outside the building in fresh air as are the connections. Duplicate cylinders are provided. This is for safety reasons and covered by strict regulation.
5.26 Portable Cylinder Heaters are not covered by these regulations and there appears to be a loophole.
5.27 The London Borough of Greenwich is not in isolation in this matter. It is not peculiar to TWA/LN flats. It applies to all systems and is a national problem.
5.28 If a safe, efficient heating system under tenants control is not installed, if the system is not economic for the tenants to use then unless an absolute ban is imposed by the Government on LPG cylinders for domestic heating through Act of Parliament it is only a matter of time before a disaster occurs.
5.29 This is not a question of working out "if it does", but waiting for "when it does". It is a point that I cannot stress strongly enough and I feel Greenwich should take this matter up through the London Boroughs Association.
6.00 Portable Liquified Petroleum Gas (LPG) Cylinder Heaters.
6.01 Like any gas LPG is safe provided safeguards are taken in its installation.
6.02 Where used for gas cookers, and fixed heating appliances the supply cylinders and connection must be outside the building in open air.
6.03 There appears to be a loophole in the regulations in this country concerning unfixed heating appliances. L.P.G. is also used by builders undertaking repair work.
6.04 The widespread use of LPG in large panel construction was first highlighted after surveys carried out by myself and Dr. Charles Wakstein at Hunslet Grange Leeds in June 1976.
6.05 Because of our concern we wrote to the Secretary of State for the Environment, the Secretary of State for Social Services and the Secretary of State for Energy.
6.06 We were concerned that because of disconnections by the Yorkshire Electricity Board many tenants had no lighting, heating or cooking facilities and the Social Services Department were issuing L.P.G. appliances and were unaware of the danger of explosion and fire.
6.07 We received a reply from the Secretary of State for Energy. In 1978, "principal suppliers of LPG advised their agents not to make cylinders of LPG available in blocks of flats and maisonettes of more than 4 storeys whatever their form of construction." Hansard written Answers 23 October 1984 col 557. para. 18.
6.08 But knowledge comes and goes. In spite of the widespread coverage by the Press both Technical and National this issue became forgotten.
6.09 In 1981 there was a serious electrical fire in Kenley Point, a 17 storey TWA block on Broadwater Farm Haringey London. The fire burnt out the mains supply with the consequence that there were no lighting, heating or cooking facilities.
6.10 Desperate times bring desperate solutions. Haringey Social Services in a humanitarian rescue operation supplied all the tenants with LPG appliances. When the supply was resumed some of them could not and still have not been accounted for. This was done in innocence by Social Services but had there been an accident where would the finger of blame have been pointed particularly after the publication of "The safe use and storage of L.P.G. in residential premises." HMSO 1976.
6.11 At the GLC Seminar on TWA at the GLC in Feb. 1985 one tenant from Ocean Estate (Morris Walk Series) stated that, "LPG cylinders are delivered to people's doorsteps like milk bottles".
6.12 The magazine 'Fire' a fire service magazine for April 1985 carries an article on LPG entitled "Unexploded Bombs' trap for unwary fireman !"
6.13 The article quotes a conference held by the Fire Prevention Association on L.P.G.
"Small quantities can give a larger volume of a flammable mixture of gas and air."
Explosions of LPG in a block of flats are likely to have very dramatic consequences both to the building and its inhabitants and also in the response of the public. We have witnessed such a response following the tragedy of the Bradford Football stand fire.
6.14 One speaker at the Conference about L.P.G. explosions stated:
"Although contribution to overall loss made by these more dramatic events is likely to be small their impact on society will be very large.
"For this reason they must be taken seriously. If their effect is disproportionate, the effects made to avoid them must be disproportionate too."
Mr. C. S. Windebank, Director of the Insurance Technical Bureau.
6.15 The article ends:
"All this increase in the use of a potentially dangerous fuel would seem to require strict control of maintenance and instruction of those using the source.
" Further are those likely to attend a leak or fire aware of the presence of the possible unexploded bomb."
6.16 The BRE Report and the Government have placed a very heavy responsibility on Local Authorities with multi-storey flats. In his reply to Nigel Spearing MP the Minister Ian Gow states that, "principal suppliers of LPG advised their agents " in 1978 against supplying LPG "to flats in blocks of more than four storeys whatever their construction."
6.17 There is a contradiction in the BRE Report which is at variance with the statement by the Minister made on 23 October 1984. The BRE Report states in conclusion para 12.15
"Those responsible should take steps to prevent the use of LPG for space heating in Type 'A' buildings (2.5 p.s.i.) over 6 storeys in height."
6.18 Thus there are two directly contradictory statements. Presumably the decision was made in 1978 about the LPG ban over 4 storeys following sound engineering advice, such a statement could hardly have been made otherwise, yet the BRE have stated that it is safe for use in TWA or similar 2.5 p.s.i. buildings up to 6 storeys.
6.19 The people to lose most over such a ban are the suppliers of LPG and they would hardly set a lower than necessary height level because they would sell less gas.
6.20 There is a serious discrepancy between the Minister's statement of 23 October 1984 and the BRE Report of 10 May 1985.
Hansard written answers cop. 557 (18) and BRE 1985 12.15.
6.21 The onus of responsibility for banning LPG in TWA 2.5 p.s.i. blocks and the many other similar blocks lies with the Government not the Local Authorities.
6.22 This matter should be dealt with by Act of Parliament before there is a serious accident involving loss of life rather than as a panic measure after one, as has happened with Wooden Grandstands in Third and Fourth Division Football Grounds.
[FIRE magazine article incorporated]
FIRE, April 1985
PHOENIX REVIEWS POTENTIAL THREAT FROM LPG
'UNEXPLODED BOMBS' TRAP
FOR UNWARY FIREMEN
Those of us who live in the country may well use LPG for cooking or heating. Indeed, an increasing use is evident on farms and cottages isolated from the normal gas mains.
While the Highly Flammable Liquids and Liquefied Petroleum Gases Regulations 1972 cover the safe handling of this power source, many are the premises that have not felt the effect of the regulations. Indeed, many a town dweller will have the odd cylinder in their premises. An unexploded bomb for the unwary fireman in the event of a fire.
My interest was once again awakened by the recent issue of the Fire Protection Association's large fire analysis for 1983. The large fire category covers fires of over £50,000 loss. Source of ignition for these fires by LPG had moved from seventh in 1982 to fourth in 1983, with losses of £3,196,000 in 1982 and £7,776,000 in 1983, more than double.
Perhaps more surprisingly, the number of large-loss fires and the loss was greater than that for normal gas main appliances and installations. Mains gas installations had fallen from 21 incidents and a loss of £4,358,000 in 1982 to eleven incidents and £1,741,000 loss in 1983, while LPG stood at 16 incidents and £3,196,000 in 1982.
Special attention
All this had been foreseen, and the Health and Safety Executive have given special attention by advice to a variety of users. The main difference in the two gases is the fact that LPG is at least one-and-a-half times heavier than air and the vapour will tend to fall to lower levels and travel considerable distances to a source of ignition. Small quantities can give a larger volume of a flammable mixture of vapour and air.
Mr. D. Barber, at an FPA Conference on LPG, in describing the chemical and physical properties of LPG, is reported as stating 'that one litre of liquid butane would expand to 233 litres of vapour and 7281 litres of gas/air mixture'.
"In practical terms", he said, "a little over four litres of liquid butane has the potential to fill a maximum capacity butane road tanker
(18 tonnes payload) with a highly combustible stoichiometric mixture of gas and air."
Thus, there is the possibility of a 'percussive, unconfined vapour cloud explosion' (PUVCE); and a 'boiling liquid expanding vapour explosion' (BLEVE). Mr. Windebank explained the mechanics of these events and set them against the background of numerous everyday incidents of a very different character.
"Although the contribution to overall loss made by these more dramatic events is likely to be small, their impact on society will be large," he said.
Need for care
"For this reason they must be taken seriously. If their effect is disproportionate, the effects made to avoid them must be disproportionate too," according to Mr. C. S. Windebank, Director of the Insurance Technical Bureau at the time.
So there is no doubt in the minds of the safety organisations of the need for great care since the product is moved by road, rail and sea and powers some mobile units.
Speaking on the sea aspect, one speaker concluded: "The best equipment in the world is useless unless it is properly maintained. The same can be said about safety procedures. They are pointless unless they are equally well understood, closely followed and carefully maintained to ensure compliance. All these aspects of safety in operations can be fulfilled only through training at all levels on board the ship and ashore.
Many farm and country premises are attracted to LPG as a power source by the low cost of installation, compared with the alternatives available—electricity, oil and coal. Compared with these fuels, the dangers are very much greater and fairly large storage requires the additional hazard of refill operations from a mobile tanker.
All this increase in the use of a potentially dangerous fuel would seem to require strict control of maintenance and instruction of those using the source.
Further, are those likely to attend a leak or fire aware of the presence of the possible unexploded bomb?
[NB: notation in margin]
[letter incorporated]
YDG-1/66.
To the Secretary of State for Energy,
The Right Honourable Anthony Wedgewood Benn, M.P.
8th July, 1976
The use of calor gas and paraffin by Local Authorities in flats liable to Progressive Collapse.
Considerable concern has been expressed in recent weeks about the rising number of disconnections made by Electricity Boards resulting from the non payment of bills.
Following a report we made to Cllr Sparling, Chairman of Leeds Housing Services Committee, on structural defects and serious fire risks at Hunslet Grange, Leeds, we also found widespread use of calor gas and paraffin in some 50 flats out of a total of 440. These fuels are supplied by Leeds Social Services Departments.
We wish to draw your attention to the widespread current practice by Social Services Departments in supplying calor gas together with paraffin to "disconnected" tenants living in flats liable to progressive collapse.
Apart from the serious fire risk there is the even greater risk of an explosion from calor gas. The Report of H. M. Inspectors of Explosives, 31st December, 1974, states (p.20) on use of L.P.G.
"The energy locked in such a cylinder is equivalent to that of several pounds of explosives, and treatment, such as heating it in a bonfire or even opening it in such a way that it is heated by the ignition of a pool of liquid ejected from it can release this energy in a catastrophic way."
We draw your attention to paras 91, 118, 148, 159 and tables 1 and 11 on pages 46 and 47 of the Ronan Point Report.
The use of L.P.G. in these buildings contradicts the findings of the 1968 Ronan Point Inquiry and its use should be banned as Towns Gas has been. Even if Social Services Departments stop supplying these fuels there is always the risk that people will take their own supplies in without realising the danger to themselves or other people.
We ask you to take steps to instruct boards to stop all disconnections forthwith and reconnect where disconnections have taken place. This action is necessary to avoid the risk of explosion in one of these buildings and the high possibility of collapse.
Sam Webb. Dip.Arch. Hons. RIBA
Senior Lecturer in Advanced Technology, School of Architecture, Canterbury.
Telephone: Canterbury 69371. Chartham 296.
Dr. Charles Wakstein. B.S., M.A., Ph.D.
2, Blenheim Crescent, Leeds. LS2 9JG.
0532 44 55 79
Copies to: The Secretary of State for Social Services, Rt. Hon. David Ennals, MP
The Secretary of State for the Environment, Rt. Hon. Peter Shore, MP
Times,
Guardian
Sunday Times
Press Association
Reuter.
[Sam Webb report continued - section 7.00]
Sam Webb ARCHITECT RIBA
Walnut Tree Cottage, 68 Shalmsford Street, Chartham, Canterbury, Kent CT4 7RH.
Telephone: Canterbury (0227) 738296.
7.00 The Fire Test at Ronan Point 18 July 1984
7.01 The fire test at Ronan Point was held as a direct result of a request by myself on behalf of the tenants. I asked that the test be carried out by the Fire Research Station.
7.02 I requested that the skirting which had been tested to BS 476 at Warrington be installed in a lounge and tested in a fire with typical tenants furniture.
7.03 All the furniture was supplied by the FRS as typical.
7.04 In view of the importance of this test I requested that measurements be taken of the load generated by this fire in the structure, the movement that would occur in joints and deflection of floor slabs etc. I asked for a film to be made and for the fire brigade to be present for safeguarding the personnel inside while the test was running.
7.05 On numerous occasions I was informed that the structure would not move, although steps were taken to monitor it.
7.06 The test was scheduled originally to run for 30 mins. The fire was put out after 12 mins.
7.07 The circumstances under which the fire was to be put out were
1. If the Fire Brigade decided that the safety of the Technical Staff could no longer be guaranteed or for any other reason of safety.
2. If the Fire Research Station's Safety Officer for this test finds it necessary to do so.
7.08 Immediately after the test was terminated the Chief Structural Engineer of Newham stated that the fire had to be put out because it was thought that if it continued Ronan Point would collapse. This was said in a Thames at One TV interview, reported in the press and subsequently stated to BBC TV Newsnight 3 August 1984.
7.09 The skirting did not prevent the passage of smoke, smoke passed through the fractured floor slab and smoke passed around the ends of the H.4 loadbearing joints from one compartment to another, i.e. between flats.
7.10 This contravenes the Building Regulations and CP3 and it would contravene the London Constructional Bylaws.
In such circumstances I can hardly see how anyone could describe that test as a success unless it was the tenants because the fire did virtually what they and I predicted.
BRE Report para. 8.2 plus the Errata slip.
7.11 In the Morris Walk series there is an added fire hazard between tenancies where the cross wall coincides with the external non loadbearing face panel. There are gaps at this intersection between tenancies. The BRE does not consider this a particular fire hazard but more of a noise nuisance. It is both.
8.00 Bowed Panels
8.01 It has often been stated that the bowing of sandwich panels was not known about until the middle of the 1960's.
8.02 On 4 / 5 October 1962 a conference was held at Church House called "Housing from the Factory" sponsored by the Cement & Concrete Association and the RIBA . The conference was opened by Sir Keith Joseph MP the Minister of Housing & Local Government.
8.03 There were papers on 'The Taylor Woodrow Anglian System' by S.V. Gardner of Anglian Building Products Ltd. and 'The LCC Housing Scheme at Woolwich' by Jack Whittle ARIBA. This was Morris Walk. problem [handwritten annotation]
8.04 There is also a specific reference to the problem [handwritten annotation over: danger] of bowing of sandwich panels in a paper by D. Bishop A.M.I.C.E. A.R.I.C.S. of the Building Research Station: "Large Panel Construction: Some general considerations."
8.05 This can be found in the text on page 58 and in the footnotes (32) following page 72.
"Miller, A.L. 'Warping of reinforced concrete due to shrinkage' Journal of the American Concrete Institute 1958."
8.06 The proceedings of this conference were published in book form.
8.07 This is not a new phenomenon and as such should have been taken into consideration by the designers of the structure so that gaps would not open up allowing smoke and in some cases flames to pass through.
8.08 Considerable discussion has taken place between myself and Fothergill & Co. over whether the outer leaf of the sandwich panels can be held solely by the bond between the concrete and polystyrene. I understand the GLC think this possible.
8.09 This hardly seems a long term solution and the BRE recommend joining the leaves by extra fixings.
8.10 In view of the fact that a number of outer leaves have fallen off Bison blocks in Birmingham and Glasgow this seems a more prudent approach.
8.11 During visits to other Morris Walk Series Estates it was noted that stair panels had bowed. Unlike the face panels these are loadbearing and hold the staircase landings up on small nibs.
8.12 In the later series TWA blocks as Eric Bunn stated in 1968 details were changed and at Aintree there is a long shelf bracket for the landings.
8.13 It is not possible to see if the lift panels have bowed.
8.14 This bowing is more serious at the top than the bottom of the stair.
8.15 I am in agreement with Fothergill & Co. over their concern relating to the stability of this part of the structure.
9.00 Conclusions and Recommendations
9.01 The history of Engineering is a study of failure. Modern Engineering developed from a scientific understanding of cracks in the Dome of St. Peters in Rome. In 1858 Robert Stephenson President of the Institution of Civil Engineers said:
"Nothing was so instructive to the younger members of the Profession, as records of accidents in large works, and of the means employed in repairing the damage.
" A faithful account of those accidents, and of the means by which the consequences were met were really more valuable than a description of the most successful works.
" The older Engineers derived their most useful stores of experience from the observations of those casualties which had occurred to their own and to other works, and it was most important that they should be faithfully recorded in the archives of the Institution".
When the history of Twentieth Century Engineering comes to be written it will revolve around the failure of Ronan Point and large panel construction.
9.02 I am in agreement with Fothergill & Co.'s Report with two exceptions.
9.03 Experience over the last seventeen years in research into large panel construction has taught me to be cautious with regard to calculations. Large panel buildings like Morris Walk are not simple to understand. A great deal of assessment relies on actual inspection of joints and judgement based on previous experience. My instinct tells me to be cautious over the actual physical condition and long term behaviour of the H.2 joint in Morris Walk or indeed any other building in the other 10 Estates in the Morris Walk Series.
I understand that the "Senior Structural Engineers in the London Boroughs Committee" have come to a similarly independent assessment and will decide at their next meeting to carry out their own independent tests on the H.2 joint. In the light of this my considered opinion is that these joints merit further investigation through opening up for inspection, before any final judgement can be made. On the 16th floor of Ronan Point the drypack was observed to be of a sandy consistency. BDP Report 4.4 C p.27.
9.04 My second exception concerns the long term behaviour of the exterior concrete leaves of the loadbearing and non loadbearing panels. If fixings are missing between the leaves I am not confident of the long term ability of the polystyrene to hold the outer concrete leaves from falling. I do not think it prudent to rely on this and these outer skins should be fixed as the BRE recommend.
9.05 The ultimate solution to these buildings may well be a question of economics. But another factor concerns the future heating system. It goes without saying that this must be safe, efficient and easy to operate. To prevent condensation reoccuring heating must be installed in every room. This will prevent condensation as the structure of the building warms over the heating cycle. Cold surfaces produce condensation.
9.06 The research carried out into Morris Walk has revealed hitherto unknown problems concerning the structure of the staircase and lift tower. There are bowed loadbearing panels on the side holding the stair landings. At the top of the building where the deadweight of the panels is less the curvature is greatest. The nibs in Morris Walk holding the landings are smaller than other estates. The GLC should check this condition on the 14 storey TWA Morris Walk blocks as a matter of urgency.
9.07 The onus of responsibility for banning LPG in TWA 2.5 p.s.i. blocks and many other similar blocks lies with the Government not the Local Authorities. This matter should be dealt with by Act of Parliament before there is a serious accident involving loss of life rather than as a panic measure after one, as has happened with Wooden Grandstands in Third and Fourth Division Football Grounds.