Sam Webb, Morris Walk Estate Greenwich, Progress Report

Morris Walk Estate Greenwich
Progress Report by Sam Webb RIBA up to Friday 8th Feb. 1985
1.00 Preliminary discussions
1.01 Discussions have been held in Peggy Middleton House with Janet Payne and Jon Clay to analyse the nature of the problems and how best to tackle them.
1.02 A list of Engineers was drawn up and firms were invited to put forward views on how they would work with the tenants and how they saw the problem.
1.03 A shortlist was drawn up and interviews were held on 17th Dec. 1984. Fothergill and Company were appointed to act as Engineers on behalf of the tenants.
2.00 Documents
2.01 Both Fothergill and myself have been supplied with a series of documents about Morris Walk. The documents I have are as follows:
1 Condition Survey - John Tilley Assocs.
2 Norman and Dawburn's Initial Report
3 Precis of N/D Report by Richard Harwood
4 Minutes of Office Meetings
26 July 1984, 14 August 1984 and 9 October 1984.
5. GLC Scientific Services Branch Report Sept. 1984.
6 Norman and Dawburn's letter with Geoscience letter
12 Oct. 1984 concerning the Radar Survey at Morris Walk.
7 Geoscience Report on Ronan Point H.2 Joints Sept. 1984.
8 Final Report by Geoscience October 1984.
9 GLC Scientific Services Branch Lab. Report October 1984.
10 GLC Report from Head of Engineering Division 6 Nov. 1984.
2.02 I have passed a number of documents to Mike Fothergill, LBG and John Mebill.
1 LCC Architects Report made in March 1962 on:
"Methods of Increasing Productivity in the Building
Industry in Relation to Housing.".
This report deals in laymen's terms on how and why the London County Council should adopt the Larsen & Nielsen system in conjunction with Taylor Woodrow.
2 Chapters from "Housing from the Factory" concerning Morris Walk Estate, the Morris Walk Series, The Taylor Woodrow Anglian System and a paper on 'Some Engineering problems of multi storey construction" by Owe Eriksson who was one of the engineers who designed the Larsen & Neilsen system.
These papers date from a conference organised jointly by the Cement and Concrete Association and the Royal Institute of British Architects in October 1962.
3 Taylor Woodrow Anglian promotional brochure on the TWA system.
This describes the system of erection, shows the joints and various plans including Morris Walk.
4 Report on the Partial Collapse of Ronan Point
for the North Thames Gas Board dated 27 May 1968.
This report was made by Bernard Clark & Partners
Consulting Engineers. Clark gave evidence at the
subsequent inquiry.
5 Article from Private Eye No 180 p.18 dated 8 Nov.
1968 which deals in part with the problems of making
joints like the H.2 joint.
6 Article from Sunday Times by Anthony Cowdy dated
3 Nov. 1968. Both these articles mention Broadwater
Farm Haringey built in TWA/LN system.
7 Report from G.L.C. Press Office dated 15 August 1968.
8 Report from GLC Press Office dated 12 November 1968.
9 Report from GLC Press Office dated 10 March 1969.
10 Pamphlet 'Fixing Method Selected for Strengthening
Tower Blocks':
'GLC's solution to Ronan Point Problem 1 April 1969.
11 Plan issued with these of one wing of Morris Walk
Series. 10 March 1969.
12 Technical Notes issued by G.L.C. March 13 1969.
13 Newspaper Cutting 14 March 1969 Daily Telegraph
" £2M Bill to make sky-flats safe."
14 G.L.C. Information notes 18 March 1969
'Progressive collapse all forms of construction.'
15 Memo from GLC Housing Architect and Director of
Housing dated 20 October 1978 concerning Morris
Walk Estate and Defective Flat Roofs due to faulty
design by Taylor Woodrow Anglian.
16 Memo from GLC Housing Architect and Director of
Housing dated 12 January 1979 concerning four other
estates in the Morris Walk Series: Jefferson Estate
Gascoyne Estate
Barley Mow Estate
Barkentine Estate
The implications of the memos on these five estates
were similar.
2.03 I have been given permission by the Minister to consult the Ronan Point Public Inquiry File. These files contain many documents with a direct bearing on the Morris Walk Series and also evidence given by various people about Morris Walk. I have made a number of visits so far.
3.00 History of documents
3.01 Some explanation of these documents and a brief history of events is required.
3.02 Early in the morning of May 16 1968 the south east corner of Ronan Point, a block of flats owned by the London Borough of Newham, collapsed. This event had worldwide implications.
Ronan Point formed one out of nine blocks of 110 flats of 66 one bed flats and 44 two bed flats 24 storeys high. The flats themselves are 22 storeys high and stand on a reinformed concrete two storey podium. This podium did not collapse.
3.03 The collapse was triggered by the failure of the loadbearing H.2 joint in the loadbearing flank wall of the flats. The failure was officially stated to have been caused by a gas explosion in flat 90 on the south east corner of the 18th floor.
3.04 James Callaghan the Home Secretary set up a Public Inquiry which met in Newham Town Hall in 21 sittings, 30 May 1968, June 18, 19, 20, 21, July 8, 9, 11, 12, 15, 16, 18, 19, 23, 24, 25, 26, 29, 30,August 1 and 2 1968.
3.05 The sittings were not consecutive because the Inquiry heard evidence from many witnesses and these fell into various groupings of, eyewitnesses, tenants, police, explosive experts, engineers and contractors etc.
3.06 One of the Engineers who gave evidence was Eric Bunn the Chief Structural Engineer to the GLC and the Engineer responsible for the Morris Walk Estate Greenwich.
3.07 During the Inquiry it became apparent that the cause of the explosion was largely academic. Although the blame for the explosion was laid at the North Thames Gas Board's door a number of other substances could have caused an explosion of the required magnitude. These were:
1. Liquified Petroleum Gas, i.e.
Calor, Propane, Camping Gaz etc.
2. Two pints of paint thinner or other similar liquids e.g.
petrol.
3. Certain aerosol containers
4. Certain types of dust explosions.
5. Electrical explosions.
6. and rather surprisingly an explosion caused by old 78 records
subjected to heat.
3.08 Other factors which could cause collapse were:
1. Impact by vehicles
2. Bad workmanship i.e. panels out of alignment or
joints failing.
3. The effect of a fire on the structure.
4. Wind damage.
3.09 What was then required to be done was to investigate the consequences of any of these factors on the structure.
3.10 It was no exaggeration when The Attorney General Sir Elwyn Jones M.P. said in opening the Public Inquiry:
"The nature of the accident that you are investigating
has caused concern extending far beyond the confines of
Newham. For by now, millions of families living in tall
blocks of flats in this country and abroad have heard about
this, and accordingly the eyes of the world will be upon this
Inquiry into the cause of this accident, and the lessons that
are to be learnt from it."
3.11 Sir Elwyn Jones was then MP for West Ham South in which Ronan Point stood. He took no further part in the Public Inquiry.
3.12 What became apparent in the weeks that followed was that no one abroad had used the Larsen & Neilsen system in quite the same way it had been used in the United Kingdom. Owe Eriksson had said in Oct. 1962 that 'longitudinal forces can be resisted without reinforcement in buildings only up to 4 storeys. Ronan Point was 22.
3.13 The licence that was obtained from L&N enabled TWA to manufacture panels of a given profile. No one else could do so. How they were put together was the responsibility of the Main Contractor T.W.A. and their Engineers Phillips Consultants Ltd. a wholly owned subsidiary of T.W.A.
3.14 TWA was jointly owned by Taylor Woodrow and Ready Mixed Concrete who owned Anglian Building Products.
3.15 The first pilot scheme in the TWA system was Morris Walk for the L.C.C. followed by ten further estates. Newham, Haringey and Westminster also had their T.W.A. schemes and in the North East there were schemes in Felling County Durham and Sunderland. According to the A.M.A. 7,951 TWA/LN flats were built, though this may well be an underestimate as no one including the D.O.E. appears to have a complete list.
3.16 To give some idea of the confusion that has arisen one London Borough recently discovered a whole estate in lowrise TWA that it didn't know about. When one considers the number of departmental changes, staff turnover and the timescale involved it is understandable that such problems occur. It is only when something goes wrong that it becomes apparent that no one knows for certain how things are put together.
4.00 Tests on Joints in 1968
4.01 During the Ronan Point Inquiry two tests were held into the strength of the H.2 joint. The first at Imperial College gave very high readings for the joint and the value of the test was queried. This test was paid for by the contractor. On the basis of this test the contractors resumed the building of what later became known as Gannon Point and Bauckham Point. These two blocks were respectively 18 storeys and 1 storey high at the time of the collapse. These two 24 storey blocks form part of the six that Newham have decided to demolish. Haringey's 19 storey block was also stopped by the collapse of Ronan Point but two weeks after the collapse the contractors resumed building. This block is known as Northolt.
4.02 In view of the criticism of this Imperial College test a full scale test rig was set up at the B.R.E. and tested after the Inquiry sittings had finished. This test showed that the loadbearing wall panel could be pushed off its bearings with a force as low as 1.8 p.s.i.
4.03 That it was appreciated that such a low force was all that was needed was known all along by the Public Inquiry. On 18th May 1968 Cleeve Barr the Chief Architect and Dr. Chan the Chief Engineer of the National Building Agency visited Ronan Point. They calculated the force at 1.4 p.s.i. This was given in evidence.
4.04 The results of the tests at the B.R.E. were published in the Press on 16.8.1968. The Government ordered every block of flats in Large Panel Construction to be checked for progressive collapse and for gas to be taken out of all flats over six storeys liable to progressive collapse. Tenants were given free electric cookers to replace their gas ones. Not unnaturally tenants all over the country reacted in attitudes ranging from fear to bewilderment for the following reasons:
1) Following the collapse of Ronan Point tenants throughout
the country were informed by councils, the MHLG and Ministers
that Ronan Point was a "one off" disaster.
2) They were told 'to leave the worrying to us'.
3) They were also told without any real checking being done
that their flats were different, stronger etc.
4.05 When the news of the gas ban was announced John Mally GLC Director of Housing announced that 'All the GLC's tall blocks are structurally sound'.
4.06 It was a statement that required some qualification. That the blocks were standing up was not in dispute. However the margin of safety of a number of the blocks was considerably below the 'norm.' These blocks include Morris Walk Estate.
4.07 In November 1968 in an almost deserted House of Commons Anthony Greenwood MP the Minister of Housing announced the findings of the Inquiry. It was the day that Richard Nixon was elected President and not unnaturally the attention of Newspaper Editors lay elsewhere.
4.08 Great play was made of a "rogue-nut" behind a gas cooker which caused the collapse. It is ironic that that cooker was the only object that Ivy Hodge received from her flat and she still uses it today.
4.09 The GLC issued another statement following the publication of the Report dated November 12 1968 in which Horace Cutler Chairman of the GLC Housing Committee said: "The 22 storey Ronan Point block is not owned and was not built by the GLC. The GLC blocks are built by a similar system but the method of jointing the panels is different and is stronger than the method used at Ronan Point."
4.10 "It would take a fire lasting for several hours to generate enough heat to endanger the stability of the block."
4.11 "On wind pressures our structural experts are satisfied that . . . the blocks are capable of withstanding the effects of a wind of 105 mph at a height of 200 feet."
4.12 "We are not satisfied at the moment that any structural works are necessary."
4.13 "The fine cracks and noises mentioned by some tenants are caused by normal thermal movement and do not indicate any structural instability."
4.14 "The last hazard is that of a chance explosion . . . is very unlikely indeed to reach sufficient force to move one of these loadbearing panels."
4.15 Apart from the statement that Ronan Point did not belong to the GLC every claim made by the Chairman of the Housing Committee was wrong and subsequent events and tests have shown this to be so.
4.16 The statements contained in Cutler's Press Release were totally at variance with the evidence submitted by Eric Bunn the Chief Engineer of the GLC who said:
"I am unable to comment on the overall stability of Ronan Point
block having not seen the calculations etc., but, as stated
above, the plan form is such that it should have an equal if not
greater factor of safety than that provided in the Morris Walk
Series."
Friday July 12 1968 Evidence p.7 at D.
4.17 The statements were also at variance with the findings of the Inquiry and evidence submitted to it, particularly in respect of wind, fire and adcidental explosions.
4.18 Eric Bunn had a meeting on July 3 1968 with Mr. Humphreys acting for the Litigation Division which instructed the Treasury Solicitor Mr. E.W. Eveleigh Q.C.
4.19 There is a note of this meeting in the Tribunal files which states:
"Mr. Bunn said that TWA would not have been formed at the time it was unless the L.C.C. had been prepared to give a substantial order in respect of this system building.
4.20 "Mr. Bunn said that his inquiries which he would have to make before writing another statement may well cause alarm since the Larsen & Neilsen system introduced by T.W.A. had undoubtedly been modified as the years went by and it could be argued that the earlier buildings were not as stable as the present ones."
4.21 "We told Mr. Bunn that the Tribunal would appreciate this and it would undoubtedly by a matter which the Tribunal would take into consideration."
4.22 "Mr. Bunn agreed to prepare a revised proof on the lines discussed with him. He will be away from 12 July until August 1 and so if he is to be called it should be during resumed hearings on or after 1 Aug."
4.23 Mr. Bunn gave evidence on 12 July 1968. The Inquiry finished on August 2nd 1968.
4.24 Following the publication of the Ronan Point Report a series of meetings were held between the panel of engineers set up by the MHLG and the National Federation of Building Trades Employers.
4.25 The outcome of these meetings in November was to arrive at two separate standards for large panel construction,
1) Existing Buildings - Ronan Point, Morris Walk etc. were
to be 'strengthened' to 2.5 p.s.i. only. Gas was to be
removed.
2) New buildings to resist 5 p.s.i. and gas left in.
4.26 The effect was to create a dual standard. The 'strengthening' later introduced was not strengthening at all but consisted of angles bolted to wall and floor junctions to resist a load of 2.5 p.s.i. applied uniformly over the surface area of the wall in the event of an explosion.
4.27 On March 10 1969 Desmond Plummer Leader of the GLC and Horace Cutler issued a further press release concerning a pilot scheme to fix these angles at Barley Mow Estate.
4.28 These angles became the basis for strengthening flats to 2.5 p.s.i. throughout the country.
4.29 In Ronan Point, due to settlement, these angles which have no fire proofing, have now been found to be holding up the floor slabs. They were never intended to do this. Neither have the walls any reinforcement to contain or transfer the enormous stresses which develop around the bolts holding the angles to the wall.
4.30 In the event of a fire of any intensity the H.2 joints in Ronan Point will move. The Morris Walk buildings are in fact less stable and the likely outcome of a fire in the corner of the block or two rooms in a Morris Walk Series block is that the wall panels will fail and part of the building will collapse. The most dangerous position for such a fire to occur is on the lower floors. This is the reason why on the advice of their Engineers the London Borough of Newham have evacuated, as a matter of urgency, the lowest 6 floors of the 5 remaining blocks in the Ronan Point Series.
4.31 The 'strengthening' angles put in in 1969 will not stop any of the structure failing in a fire of any significance. If the structure starts to move. The amount of movement that can take place before collapse is not very great and the margin between stability and instability is very fine. This type of failure is known as "catastrophic collapse". See para. 148 of Ronan Point Report 1968.
4.32 With regard to the ability of Morris Walk to withstand winds of 105 mph at a height of 200 feet. Ronan Point most certainly could not take this wind load.
4.33 Ronan Point was designed to exposure grade C, i.e. 24 p.s.f. and the Inquiry made specific requests that it be strengthened to take 105 mph wind loads in the upper corners of the block to avoid panels being sucked out.
4.34 Morris Walk was designed to exposure grade B, i.e. 17 p.s.f. a lower strength than Ronan Point. See para. 30 and 132-147 of the Ronan Point Report 1968.
4.35 It would follow that the claims made by the GLC about wind in 1968 are open to question. The fact that the blocks at Morris Walk are only 10 storeys high does not mean that they stand on level ground, they rise up a hill. The top floors of the 10 storey blocks furthest up the hill may well be the equivalent of blocks of say 15 floors on level ground close to sea level.
4.36 The codes of practice on wind loading were revised upwards after the publication of the Ronan Point Report in 1968.
5.00 MORRIS WALK SERIES OF ESTATES
Built by The London County Council and
The Greater London Council
Compiled from G.L.C. List of 1976
5.01 Completed by 1966
1. Morris Walk Estate Harden St. S.E.18
562 Dwellings
L.B. Greenwich
2. Argyle Estate Wimbledon Park Road S.W.19
120 Dwellings
L.B. Wandsworth
5.02 Completed by 1967
3. St. Matthews Estate Brixton Hill S.W.2.
196 Dwellings
4. Barkentine Estate Alpha Grove E.14
40 Dwellings
L.B. Tower Hamlets
5. Ocean Estate Cayley Street E.1
120 Dwellings
L.B. Tower Hamlets
6. Jefferson Estate St. Leonards Street Bow E.3
80 Dwellings
L.B. Tower Hamlets
5.03 Completed by 1969
7. Barley Mow Estate Three Colt Street E.1
240 Dwellings
L.B. Tower Hamlets
8. Gascoyne Estate Bradstock Road E.9
160 Dwellings
L.B. Hackney
5.04 Completed by 1969/70
9. Aintree Estate Hartopp Avenue S.W.6
112 Dwellings
L.B. Hammersmith and Fulham
5.05 Completed by 1970/1
10. Ledbury Estate Camelot Street S.E.15
224 Dwellings
5.06 Completion date not shown on GLC List
11. Lethbridge Estate Drysdale Road S.E.13
240 Dwellings
5.07 Estates 1 - 9 excluding Barley Mow are included in the G.L.C. list given in their Press Release March 10 1969 No 140 and were occupied when the 2.5 p.s.i. "strengthening" procedures were announced. The pilot scheme for "strengthening" was Barley Mow.
5.08 There are four further TWA/LN Estates in London.
5.09 Newham - Freemasons Road Estate
Ronan Point Series
990 Dwellings
Vicarage Lane Estate
5.10 Haringey - Broadwater Farm Estate
5.11 Westminster - Lisson Green Estate.
6.00 Work in hand
6.01 It is proposed to make relief models of joints running along the block from living room to living room approx. North South and at right angles to this through the stair core.
6.02 It is proposed to make a 1:50 model of the block and a model of various joints to one quarter full size.
6.03 Visits will be made to the other ten Morris Walk Estates. A list of these is enclosed. The estates vary in a number of respects, condition of the concrete, details of structure, and movement cracking etc.
6.04 I desperately need drawings to carry out this work. Before Janet Payne went on leave she promised these. However when I had a meeting with Mike Fothergill I was surprised to find that he did not have a complete set. He did not have drawings of any joints, only of panels. I explained how the units were fixed together as best I could but this is no substitute for the actual drawings.
6.05 We have contacts with tenants on some estates and a good relationship with tenants at the Aintree Estate.
6.06 These surveys will be mounted on boards for display.
6.07 I will continue my research into the Ronan Point Inquiry Files.
6.08 I have proposed to John McGill and Tiny Batt the tenants representatives and JohnClay the T.L.O. that we organise a seminar to discuss what we are doing.
6.09 The question of the use of L.P.G. on estates is a very serious one. The Shelter organisation approached me after the Putney explosion because I had warned of this danger in an article in The Guardian. Governments have made pious noises about the problem over the years but little else. In the Ronan Point Files I came across the following:
"The storage and use of all liquid, solid and gaseous combustible
materials, in the present state of knowledge of the safety of the
installations, are forbidden inside blocks, except as provided to
the contrary in the present regulations."
Decree of the French Council of State dated 15.11.1967 in relation
to tall blocks.
In Israel too, such cylinders and gas bottles are banned inside all buildings. Probably most E.E.C. countries have similar regulations to France.
6.10 I aim to have questions raised in Parliament about this. If people had proper forms of heating then they would not have to resort to dangerous fuels. If a calor gas bottle exploded in Morris Walk one side of the block would fall down.
6.11 This report and notes are interim.
They are sent to John McGill
Tiny Batt
Jon Clay
Mr. Nind
Mike Fothergill
Sam Webb RIBA Feb. 9 1985