Sam Webb and Dr. Charles Wakstein, Hunslet Grange Leeds - Joint Report

Hunslet Grange Leeds - Joint Report by Sam Webb and Dr. Charles Wakstein on flats visited 14th/15th July 1976.
Previous Reports: 1. 12 June 1976 by Sam Webb as requested by Councillor Sparling, Chairman Housing Services Committee.
2. 15 June 1976 by Charles Wakstein as requested by Councillor Sparling.
3. Letter of 25 June 1976 Sam Webb to Councillor Sparling.
4. Letter of 26 June 1976 Sam Webb to Councillor Sparling enclosing report BRE CP 24/76 "the Response of Buildings to accidental Explosions" by R.J. Mainstone.
5. Report by J.E. Slack FP4/2/3 28 June 1976 Fire Service Bradford.
6. Letter of 4 July 1976 Sam Webb and Charles Wakstein to J.E. Slack.
7. Joint Report Sam Webb and Charles Wakstein on J.E. Slack's report.
1.00 Introduction
On 14/15 July together with representatives of H.G.H.A.G. we visited a number of flats. The problems of damp, draughts, and rain penetration are inseparable from those of fire risk, deterioration of the structure, cracking between panels, bowing of exterior panels, missing or inadequate drypack and dangers of progressive collaspe. These faults are symtoms of the same common cause.
1.01 Our comments on fire risk and risk of explosion from liquified petroleum gas are contained in our joint report (7). In view of the evidence of Her Majesty's Inspectors of Explosions and the Ronan Point Report etc. we do not accept Mr. Slack's views on explosions concerning L.P.G., venting through windows. As stated in our joint report 15 July 1976 (7) we found a 32 lb. Calor Gas cylinder in Hunslet Grange. The behaviour of a cylinder of this size in a fire is graphically described in H.M.I. of Explosives Report of 1974.
2.00 We visited a number of flats to carry out further surveys to those contained in our previous reports (1) and (2).
2.01 96 Rylstone Lawn - gable end flat, three bedroom maisonette.
There was a 10lb Calor Gas cylinder, a cooking unit and a heater. The heater had no "on/off knob". The only way to control the gas was by turning the knob on the cylinder. We do not consider this to be a very safe heater. The above equipment was supplied by Social Services and had been in the flat for a year.
There are the following cracks in the structure:
1. In the double bedroom ceiling, between the floor slabs, this continued into the next room, and ran the full span.
2. Parallel to this about 50mm (2") from the partition. This runs for the full span.
3. Parallel to the loadbearing gable end wall, 50mm from the wall. This runs the full length of the wall.
4. Vertical crack, down wall at junction of partition, and gable end wall in double bedroom.
5. In the living room ceiling, parallel to window, runs the full span.
6. In small bedroom with corner cupboard. There is a ceiling crack between slabs which turns at 90° some 50mm from load-bearing compartment wall.
7. We tested the cracks in (6) for depth. They were 37mm to 50mm deep.
This flat does not comply with Sections E9(1) or E9(2) of the Building Regulations.
2.02 18 Stafford Chase - top floor gable end maisonette
We are seriously concerned by this flat. Since the flat had recently been visited by council officials some "repair" work has been carried out in the double bedroom. The nature of this "repair" work, i.e., filling of deep cracks between the panels with carlite plaster leads us to believe that whoever authorised this work does not understand the magnitude of the problem. We hope that some note was made of the depth and width of these cracks. The plaster is already beginning to fail and the work can only be described as "bodged".
There is a very serious crack in the end of the wall panel under the window in the boxroom. This repeats at the lower level in the kitchen. The concrete is spalling, we found similar cracks in other flats.
The kitchen floor of this flat slopes and corresponds with the cantilever over the walkway which sags. The slope can be simply tested by placing a marble on the floor in the kitchen or on the table and it will roll towards the window.
There is a bowed panel over the kitchen window.
In the top bedroom at the junction of the ceiling, gable end wall and window there is a deep hole. Water enters the flat at this point. From the balcony it is possible to see that the movement of the concrete units have caused the weathering gasket to fracture.
We consider this flat to be a dangerous structure.
2.03 1 Larchfield Dene
There is a vertical crack through the loadbearing wall between the bedroom and the living room. It was possible to blow air through this crack. There are cracks in the ceiling.
In the kitchen there are pipes passing from the duct. The hole through which the waste pipe passes is twice the diameter of the pipe. This does not comply with Regulation E 14.
Inside this duct there is no effective fire stopping at all between the floors. A fire in this flat at ground level could enter the duct and spread fire and smoke to any of the other flats above. It is extremely dangerous and cannot be held to comply in any sense with CP 3 Chap. 4 or Part E of the building regulations.
Apart from the danger of fire, if a tenant was using L.P.G. for cooking, and the [illegible text] appliance was in anyway defective then if leaking gas [illegible text] entered this duct the resulting explosion might well be catastrophic. We refer you to Mainstone's Report, "The Response of Buildings to Accidental Explosions" (4).
There appears to be water leaking down the back of this duct.
2.04 20 Endon Croft
There has been a fire in the duct at some time involving a fuse box.
There is a crack in the bathroom ceiling. In the two bedrooms we found serious drypack failure where the panel under the windows had bowed. The bowing [panel] had caused the wall to move out at least 12mm (½") in the centre. This could be seen by the drypack on the floor which formed a small ledge proud of the inner wall face. There were gaps under the wall for a considerable length where it had lifted off the drypack. There were gaps 100mm(4") deep under [this wall], right through to the polystyrene.
We found drypack failure under both the loadbearing walls approximately 1 000 (1m) back from the windows.
In the Kitchen there was drypack failure under the window.
2.05 External Inspection of Endon Croft
From the top floor access balcony it is possible to see the extent of the bowing of panels. The entire run of panels except for the end ones are seriously bowed outwards, for the two storeys above the walkway. The end panels which are relatively straight appear to be pushing the gable end walls out.
From the ground both ends of the balcony returns are seriously out of alignment. The balcony units have become offset by at least 25mm(1").
Above the front doors of no. 2 and no. 43 Endon Croft the concrete panels are seriously bowed.
If the structural defects we have found at Endon Croft are getting worse then we can see a situation where the building may collapse when the loads become too onerous for the ends of the structural members.
We cannot see how these bowed panels can be replaced without major engineering work.
The external inspection of Endon Croft shows manifestations of faults we have seen on all the blocks and we selected it at random.
2.06 73 Leek Chase - gable end flat
In the lounge there is a hole in the drypack 100mm deep in the gable end wall. This is immediately under the left hand side of the wall mounted electric fire.
The windowwall is seriously bowed and there is drypack failure under it as in 20 Endon Croft. There are gaps 100mm deep. The base of this panel has spalled off pieces of concrete.
The drypack has been mended at some time in the bedroom under the loadbearing wall. When has this been repaired and for what reason?
This flat does not appear to have been strengthened.
2.07 42 Stafford Chase
An inspection was made of the duct from the bathroom. The fire stopping is inadequate floor to floor and from the duct to the bathroom.
The comments in para. 2.03 apply to this duct as well.
3.00 Conclusions
As stated in the introduction 1.00: "the problems of damp, draughts and rain penetration are inseparable from those of fire risk, deterioration of the structure, cracking between panels, bowing of external panels, missing or inadequate dry-pack and dangers of progressive collapse. The faults are symptoms of the same common cause."
SW/CW 19 July 1976