Sam Webb, Report on conditions at Hunslet Grange Flats, Leeds

ARCHIVE DOCUMENT
10 June 1976
Start of document

Report on conditions at Hunslet Grange Flats Leeds found on 9th and 10th June 1976 requested by Cllr Sparling Chairman of the Housing Services Committee.

1.00    At the invitation of the Hunslet Grange Heating Action Group I was invited to address a meeting on 9 June.

1.01    Before addressing the meeting I asked to visit the flats to inspect defects that had been reported to me.

43 Stafford Chase

2.00    The first flat visited was 43 Stafford Chase where Mrs V. Hooper lived. The people present were Dr Charles Wakstein, Mrs Hooper, representatives of the HGHAG, and a reporter from the Yorkshire Post who had been invited by the Action Group.

2.01    In the kitchen at the junction of the external wall panel and the floor was a gap of some 12" (300mm) from which drypack was missing. I was told that people with long fingers could touch the polystyrene insulation. I could push my fingers into the gap under the wall. I inserted a ruler and could feel it touching the polystyrene. The ruler penetrated just over 4".

2.02    Charles Wakstein had removed a piece of drypack from this gap on 6 June. I found loose drypack. Dr Wakstein showed the drypack to Councillor Gabb who was at the meeting. The height of the dry-pack varied being higher on one side of the building than the other.

2.03    I noticed some other cracks in the drypack and when pushed, the mortar moved. I pulled a piece 6" long (150) from the wall with my fingers. It was 1" high (25mm) and between ½" and ¼" thick (12½ and 6mm). Attached to it was a large piece of newspaper and this was obviously put in when remedial work had taken place, because it was bonded to the mortar. I gave half to the reporter & showed the other piece to Councillor Gabb at the meeting.

2.04    A very severe draught came through the gap from the outside. This could be felt 3 or 4 feet back from the skirting. I have no doubt that rain penetrates the structure at this point. There is also danger from frost damage.

2.05    From ground level it was possible to see considerable bowing of [a] panel (by at least 1½" in the middle). This panel was above the kitchen window.

2.06    At this point I asked if there were any cracks in the structural walls or ceilings. Mrs Hooper showed me cracks in the bathroom wall and ceiling.

2.07    These cracks ran from the top of the basin and had torn the vinyl splash back and wallpaper. They extended across the ceiling and down the wall on the staircase side, ie across the entire span of the [illegible] floor unit.

2.08    I found it possible to push a penknife and a flat bladed kitchen knife up to 13¼" into the wall and the ceiling cracks. This was done without difficulty and I asked the reporter to pull out the knives.

2.09    There were other similar cracks in the living room ceiling and in the bedroom ceiling on the other side of the flat. The flat was a maisonette.

3.00    I thought that I should inspect another flat either above or below the one that I was in, to see if there were similar signs of failure.

3.01    42 Stafford Close
This was a single floor two bedroom flat. Cracks in the bathroom were identical to those in the maisonette and travelled up the wall, across the ceiling and down to the stair wall.

3.02    There were cracks in the bedroom ceilings and in the living room ceiling. These ran the entire width of the flat.

3.03    The tenants had stuck wide adhesive tape along the outside wall floor junction to stop draughts and damp.

4.00    The Meeting 8pm June 9 1976.
Flats 42 and 43 Stafford Close.
I stated at the meeting that these flats did not conform to the British Standard Code of Practice CP3: Chapter IV (1962) Precautions against fire in Flats & Maisonettes over 80ft.

4.01    The introduction states inter alia:
"It should be noted that in this part of the Code the recommendations apply to all the floors of a building and not only those floors which are in excess of 80ft from the ground. It may be found that little or no inconvenience or additional expense will be incurred if buildings less than 80ft are designed on the principles set down in this Code for higher buildings"
It would appear that the "means of escape," do comply with the Code.

4.02    Where the building does not comply is that separate [tenancies] do not have adequate physical separation to prevent the passage of fire from one unit to another. The cracks I found will allow this to happen.

4.03    Internal means of escape inside the flat could be jeopardised by smoke, flames, fumes or a combination of all three, coming from a fire in another flat.

4.04    It may be that there was adequate physical separation when the flats were built. It is not there in flat 42 & 43 Stafford Close now and something has happened to the building since completion.

4.05    The physical separation required by the Building Regulations for England and Wales is not met, and if the buildings were inspected today I cannot see how a Building Inspector could certify that flats 42 & 43 meet the regulations under which the flats were built.

4.06    Since Ronan Point collapsed regulations have been tightened, CP3 Chap IV has been revised, it now applies to all multi storey flats and would apply to Hunslet Grange. Part E and EE of the regulations have also been revised.

4.07    It states in the Ronan Point Report para 148 that the heat from an ordinary domestic fire would cause a floor slab in that building to arch. This could cause a collapse.

4.08    Many people in Hunslet Grange appear to be using paraffin and or Calor gas for heating, cooking and in some cases lighting. I do not wish to comment on the reasons why but there is a very high fire risk, and risk of an explosion.

4.09    Because of the state of the structure a fire could cause a collapse of one or more end units. As the building gets older, this risk increases. (4.07)

4.10    After the meeting was thrown open to questions Councillor Gabb agreed to take up the matters raised with the Housing Committee of which he said he was a member.
A number of tenants in the audience told of many things that corresponded with what I had been told by the tenants of flats 42 & 43 Stafford Chase.

1. Water penetration from outside at floor, wall & ceiling junctions
2. Water penetration, flat to flat through floors and walls.
3. Outside gable end walls leaked
4. A vicar in the audience said he stuck sellotape over the cracks in his wall when he lived in the flats.
5. Everyone said how high the heating bills were, some in the region of £100 a quarter.
6. Cooking smells came up the bathroom duct.
7. Fears were voiced about the bathroom pipe duct and some people said it was not blocked off at each floor. I don't know if this is so, but if it is, it constitutes a serious fire risk.
8. People heard noises in the flats coming from the structure. I asked the people in 42 & 43 if they could hear noises, I didn't say why, and was told they could hear the building 'cracking' at night. I will come to this point later.

5.00    Visit on 10 June 1976.
Another visit was paid on Thursday with Dr Wakstein and a structural engineer Mr David Yeomans of Liverpool.

5.01    We noticed two men on a cradle repairing the edge facing of a load bearing wall between two flats. Another edge of a wall had been repaired & the open joints between the spandrel panels filled with mastic.

5.02    While walking towards Milner Chase Flats Mr Yeomans noticed that the gable end wall near flats 27-46 etc bowed out half way up near the walkway bridge. It could be clearly seen from the ground that the gable end junction and edge of the panel, to the walkway, was wider at the top than at the bottom.

5.03    The inside column supporting the bridge appeared to be out of [alignment] plumb when lined up with Ashbourne Croft behind.

6.00    32 Ledsham Dene.
Cracks were inspected in the stair well. There were both vertical and horizontal. Water had penetration through the joints from the adjoining tenants bathroom.

        The penetration caused damage to the wallpaper. This had been stripped, the hole stopped, the wall repaired but water still came through, damaging the paper. The crack is half way up and corresponds with the floor level.

6.01    32 Leek Chase.
This flat had a crack in the inside of the gable end wall, through which water entered. This corresponded with the outside joint. The (neoprene) weather strip was missing at the bottom of this unit & did not cover the lower one so water penetrated. Someone has put mortar on this joint at sometime on the outside.

7.00    Conclusions.
Severe movement has taken place in Stafford Close. This has probably been caused by shrinkage of the units, hence the tearing of the vinyl splash backs in flats 42&43.

7.01    I think these cracks will be found in other blocks as well. A structural survey will show whether a pattern of failure exists and if there are any abnormalities to the cracking such as diagonal cracking of panels.

7.02    The cracks enable fire to pass from unit to unit. This will occur through floors and walls and does not comply with acceptable safety standards laid down in the Regulations. This has occurred since the buildings were built.

7.03    The building is moving. The noises that tenants report are caused by this in some cases. Normally this would not be too important in a continuous structure. In this structure it is, for the following reasons.

7.04    All forms of concrete construction in buildings take the form of rigid structures particularly at the joints where stresses are higher than in other areas. Therefore, if the tying together of the joints by reinforcement is not provided [for] at the joints then some movement will take place. Any 'drypack' or inside concrete becomes a disconnected mass, at best adhering to one member, but never to more than one.

7.05    The joint then reverts to a system of members supported by each other, by gravity and if these conditions are too onerous for the ends of the individual members, commencement of collapse conditions are initiated at the first sign of movement.

7.06    As the units become disconnected the stability of the building is impaired and the building will not behave under loading as it was designed to behave. It behaves like a "house of cards."
Extracts from "Comité Européen du Béton, Information Bulletin No 60" are as follows:
2.1. General organisation of the structure
"One can hardly over-emphasise the absolute necessity of effectively joining the various components of the structure together in order to obviate any possible tendency for it to behave like a 'house of cards' and of organising the structure accordingly. In this respect it would appear to be of major importance to install mechanically continuous steel ties inter-connecting opposite walls or facades and providing safeguards for all the vertical panels."
This was translated into English only after Ronan Point collapsed and it was submitted as evidence to that Public Inquiry in 1968.

7.07    The information bulletin points out in paragraph 3.2, problems connected with large panel construction when it fails.
".... the brittle character of some kinds of failure (panels, horizontal joints, wind-bracing elements, certain vertical joints) or the uncertain character of the effectiveness of certain devices (keyed joints) is emphatically pointed out. The added risk that these constructional features entail for the structures warrant the desirability of providing higher factors of safety for the relevant parts than are usually adopted for structures in which such features do not occur."

7.08    Para 4.4. Brittle failure states:
"It is necessary to emphasise the fact that when failure of a loadbearing wall - whether it occurs in a joint or in a panel - takes place, there is no possibility of a favourable redistribution of forces nor of further sustaining the load. The brittle character of such failure justifies the adoption of high factors of safety."

7.09    When a building of this type of construction fails there is little or no warning - cf Precast concrete staircase at Hounston, Camden School for Girls School Hall, Army Buildings at Aldershot. Although none of these buildings were built using the YDG system the structural philosophy is the same.

7.10    Failure has already begun to take place in flats 42 and 43 Stafford Close. The fact that it is possible to insert a knife blade into what appears to be a joint between panels shows that failure in bond has occurred. If this is not a joint, but a crack in the panel, then the failure is even more serious. Failure has occurred also at 32 Ledsham Dene in the vertical and horizontal joints. (para 6.00).

7.11    In the long term this shrinkage movement could cause collapse, if it is widespread throughout the flats. Parts of the buildings have already become a "house of cards." If these conditions are found at gable ends then they are very serious indeed, and under certain wind loading conditions wall panels could be sucked off at the gable ends. I refer to the conditions found up under the bearing surface of the wall panel in the kitchen of 43 Stafford Close. These panels are beginning to behave in way that was not envisaged when the building was designed. It should not be possible to move drypack in these buildings let alone pull it out. Investigation must be carried on the dry pack shrinkage and the bowing of slabs.

7.12    The use of paraffin and Calor gas greatly increases fire risk. If there is a fire in a flat with calor gas cylinders present there will be an explosion. In a building of this type of construction, the consequences of this happening are very serious. If it occurs at the ends of the building the structure may well collapse. This is an unacceptable risk in a building of this kind housing as it does, so many people. It is quite pointless removing town gas from these buildings if people are going to take calor gas [illegible text] in because they cannot afford the electricity for heat light and cooking.

7.13    In [these] present conditions an ordinary domestic fire could pass from flat to flat, this does not comply with either the regulations in force when these flats were built or those in force now. (See 7.02)

8.00    Recommendations.
What ultimately happens now rests with you, the Members of Leeds Housing Services Committee. I have been asked by your Chairman Councillor Sparling to report on my findings to you. The faults I have outlined have occurred since these flats were built.

8.01    The responsibility you have to the tenants of these flats is a very heavy one. You are responsible for their safety.

8.02    The advice I have given you is given fully in the same spirit it was given to the tenants and I am sending a copy of this Report to the Heating Action Group.

8.03    I recommend that you approach the President of the Institute of Structural Engineers and request that he appoints an independent Structural Engineer to look into, the [illegible text] safety aspects of Hunslet Grange and [illegible text].

Sam Webb Dip Arch (Hons) RIBA
Member of RIBA Services Committee
Member of RIBA Building Control Panel
Member of RIBA Council 1975-76.
12 June 1976.