Notes on Inquiry

ARCHIVE DOCUMENT
Not stated
26 July 1968

21 May asks if an R.P. can be improved, saved.

B says impossible to say without the contractor having
a full examination.

(But yesterday the contractor declared, for all the world
to hear, that R.P. is perfectly safe.)

HOPKINS - My learned friend Mr. Purchas jumped his place
in the queue.

The celebrated Joint H 2. Page 17B - the famous H 2 joint.

(We should put its portrait in the Academy - JL)

H - The screed shows the maximum amplitude of variation?

B - Correct.

22 Questions about temperature variation in screed,
conductivity of concrete,

23 conductivity of polystyrene.

24 H - Much obliged.

Difference between words 'much' and 'substantially'
explored.

Whether or not its a concrete roof, they haven't been
told but assume that it is.

Lowest temperature 20 degrees F.

Highest temperature 110 degrees F.

Roof most dangerous from structural point of view.

25 Roof gets most effect over course of time.

Shutting off of heat 3 days before collapse had no
significant effect.

B is now being treated like the oracle.

Barnes, N.F.B.T.E., asks about one type of system building
mentioned in Dr. Chan's report in which there would not be
a collapse of floors above an explosion.

Bowen has not had opportunity during last 2 evenings
really to examine this document.