IMG_0895

Notes on Inquiry

ARCHIVE DOCUMENT
Not stated
23 July 1968

57 He has not been back to the site since the collapse.

58 Machin - supervision on site.
Ho - 7 or 8 to a team efficient, and accustomed to this
kind of erection.
Any particular form of construction? Unskilled men?
Ho - I do not know. I think some of the men did work
on other sites before this one.

Instructions passed on by erection manager.
Assistant erection manager and general foreman, permanently on
site; responsible for erection alone, in all blocks.

I think there was a chargehand for each block as well.

59 During inspection by experts it was discovered that on
the fourth floor there was a gap between right hand tie
plate and floors of 3/8".
Ho - No gap during my inspection. I did not see any
case like this.

Twice asked if it was because bolt had not been properly
tightened down.
Ho - not necessary. It could be due to pressure on the
other end of the plate, the end under the wall.

60,61 The plate. Do you follow?

Ho - Or further compression of the hardboard pads?

Machin - Were the men not carrying out their erecting
jobs properly?

Ho - I do not think there would be many cases where they
were not ...

If you found many bolts not fully tightened you would assume
this?

Ho - Yes.

Machin - Lack of supervision on the part of the chargehand?

GRIFFITHS INTERVENES, says this is COMMENT.

62 Ho does not follow, does not know to which point they are
referring etc.

LAYFIELD cross-examines.

Report: Early July 7th floor completed. 2 lines further
down - beginning of August 18th floor completed.

Re-examined by Butcher.