Q Your full name is Bank, Maurice Bowen. (GIVES HIS TITLES+HONOURS)

A The last two on this are wrong. I am Associate Member of Instutite of
Mechn. Eng. and a Member of Ass. of Con. Eng.

LAYFIELD
Thank you. P.P.Inst. of Struct.Eng. and among other things an examiner
for qualifying examinations of District Surveyors.
Your firm have been concerned with the Shell Building. Commercial Union
building, of the order of 400 ft. New Zealand House. You were appointed
by the Gas Council to advise on the structural aspect of the Roann Point
collapse.

A Correct.

Q You refer to the roof first of all Mr. Bown. What is the point to be
observed about that.

A Well, that it is still there.

Q You comment on the fact that a non-loading bearing wall from the 17th
might down to the podium has remained.

A In my experience there is an element of luck in that the debris can sometimes
fall in such a way as to asist other parts to stand up.

Q That is your item, fortuitous disposal and wedging of debris
against partition walls?

A Correct. I think it likely that the chuting effect, or perhaps I should
say tobogganing, because reference has been made to one man tobogganing
down the entire collapse of the 17th floor (points to photograph), that
floor slab can be seen clearly with a whited edge.

Q The forming of a sort of chute.

A Yes. It probably helped a great deal.

The performance of distribution steel is noteworthy. In some cases
electric conduits played a significant part. If there had been more
distribution steel it would have been even stronger. The joints between
floor units appear to have broken and failed utterly. Horizontal joints
at each floor between external well and floor units likewise failed
utterly. The factory made floor and wall units inspected appeared
generally well made and of good concrete. The bonding was of such
quality that the filling could be broken off with fingers using little
force. The filling was inadequate and the quality doubtful. There
appears to be evidence of rotation at the ends of the slabs. Lengths
of joint reinforcing bars were seen hanging and apparently rusty, otherwise
notably free from insitu concrete filling. The weakest joints are the
insitu, especially D (check). The design approach is not unusual but it
is common practice to insert anti crack reinforcement at the top ends of
the slabs. The absence of such reinforcement probably affected the mode
of collapse. In this photograph if we lookm at the partition wall,
which is the outermost wall remaining, I place this in my mind in
rather the same category as the fortuitous tea break at Aldershot at the
Power Station collapse. That is to say, there, but for the grece of
God, how many people couldhave been killed. I would be concerned with
the effects from floor heating of the type installed in Ronan Point,
not in the early life of the building, but in the longer term.

End of document