YAL: May I just think about that for a moment ?
RYAN: Please do.
YAL: No. These hinges could not have been on a door hung the
other way.
BURGOYNE: So the explosion moved out from the kitchen.
SUR: In to the kitchen. It moved along the passage and into the
kitchen. The maximum shock was in the bedroom and living room
BUR: And we do not know what it was (6, page 59)
REID(p.21): The doors to the flats on the 18th had been blown off
or damaged and forced inwards. In Flat 90 there had been an
explosion and a fire in addition to the structural collapse
which had affected all flats in that corner. Note the charring
to the wall behind the sink unit
MAY: Did you inspect the taps of that cooker ?
REID: Yes, they were off (page 71,3 or 5)
MAY: All of them.
REID: They were the type you push in to turn them with a bar to
tell you whether they are off or on. The cooker had been thrown
on to its face and wrenched the flexible gas pipe from the
fixed supply pipe.
SUR: The cooker was lying on debris. If it had caused the explosion
the debris would have been on top of it.
GRIF: At the moment we have the advantage of a distinguished body
of gas and explosion engineers. I rather hoped you might get
together and have a full and frank discussion and see if it
is possible to arrive at a unanimous view or at least narrow
the range of dispute.
EVE: It is a great pity that the tests on the nut, on the union and
the dilution and ventilation tests have ceased.
GRIF: If the experts arrive at the unanimous view that the tests
are necessary then of course they must be done. I hope heaven