GRIFF I think Mr. John Robert Kell CBE CEng MiMechE PPIHVE FinstF
will now explain the whine to the satisfaction of this court.

KELL I inspected the ventilation on the 20th June. The belt guard
to No. 1 extractor fan on the roof, which is connected by metal
ducts to 4 vertical shafts, which connect at each floor to
grilles in the bathrooms and toilets was made without provision
fot the fan and themdor shafts and the installer appears to have
cut the wires to clear the shafts. The bolts were missing
in No. 1 guard, hence the upper part of the guard was loose,
and rubbing on the shafts. The ensuing noise transmitted by
the structure could well be described as like an electric
drill. Mechanical vibration was intended to be isolated by a
layer of cork in the concrete bed of the fan. In forming of the
beds, however, cement had been allowed to skim over the cork,
short-circuiting it to some extent, a fault in execution.
Furthermore, the electric conduit to the motor is firmly
clipped to the concrete base and the floor concrete, thus again
forming a path for transmission.

The upper half of No. 2 fan was located with a single bolt
which was without a nut. No. 2 fan was not running.

With regard to the bearing, No. 1 fan was bearing low on oil but
not dry. No. 2 motor, oil in the bearing had suspicions of
some fine foreign substance in it. This might be builder's
dust. No. 2 slightly out of line causing slight squeaking in
starting and stopping. There ware nameplates on the fans.

PURCHAS Mr. Kell, the ventilation went to areas from the bathrooms
and lavatories through a series of ducts, there was a
different system to take away air in the area of the building
near the refuse chute.

KELL 5 That is right.

PURCHASE And there is no inter-communication between the two?

KELL No.

PURCHAS But one must also remember that there is a natural
ventilation available to everybody in the flats, is there
not, by opening the windows?

KELL Indeed. I should also like to point out that no expansion
and contraction had been allowed for in the main soil pipe.

End of document