WESA_1_5_03

Extracts from 'The Structure of Ronan Point and Other TWA Buildings', BRE Report, 1985

ARCHIVE DOCUMENT
Not stated
8 September 1985

HAND-DRAWN DIAGRAM
Title: Typical layout plan of a 16-storey block with 6 flats per floor.

[Floor plan text labels:]
Living room, Bedroom 2, Bedroom 1, Kitchen, Bath, Hall, Staircase, Refuse, Lift lobby, Lift.
Flat types: 3-person flat, 2-person flat, 3-person flat.

FLOOR PANEL JOINT:
The 1/8" gap between panels is a tolerance; the panels are usually butted together and left without filling the underside. The shear key castellation is shown dotted.
Site reinforcement. Site concrete. Floor slab.

PARTITION, FLOOR AND CEILING JOINTS:
The partitions are not supplied with projecting lifting bolts; levelling is carried out on removable packs and stability is supplied by the vertical joints at each end of the partition. At ceiling level, lime mortar and fibreglass are specified to ensure that load is not transmitted to the partition underneath and to localise any cracks.

Floor slab. Partition. Dry mortar pack. Lime mortar. Fibreglass.

End of document
WESA_1_5_03
3 of 3