WESA_1_11_04p1

Letter from Building Research Advisory Service to London Borough of Newham

ARCHIVE DOCUMENT
Borehamwood, Hertfordshire, WD6 2BL
4 May 1984
Start of document

Building Research Advisory Service
Building Research Establishment
Fire Research Station
Borehamwood, Hertfordshire, WD6 2BL

Telephone 01-953 6177 Telex E951648

telephone extension 370

London Borough of Newham your reference DDES/GPW
25 Nelson Street
EAST HAM our reference: A16 FCA/IC 3305
London E6 4EH
date: 4 May 1984

For the attention of Mr Stratford

Dear Sir

I am writing with regard to our recent discussion concerning the remedial work
at the Taylor Woodrow Anglian Type Tower Blocks where separation between the
external wall panels and the floor construction highlights a problem in respect
of structural fire protection. According to the information presented to me the
situation is that the nominal clearance existing between the wall panels and the
floor in the lounge area ranges from zero to 7 mm, and in respect of the bedroom/
kitchen situation the clearance is much finer and 1.5 mm reflects the average
situation. These clearances are maximum at mid-span condition and diminish
progressively towards the extremes of the wall slab.

On the understanding that these clearances remain relatively constant and the
floor construction is of the requisite fire resistance, namely 1 hour, then we are
pleased to confirm that the remedial treatment discussed and agreed with you,
which is shown on drawing Nos H1840/3 and /4 would be adequate in the circumstances.
The first aspect to take into account is that of fire resistance as defined in
BS476 : Part 8 where judgement would be made in terms of 'integrity'. Under test,
which represents the fully established fire condition, loss of integrity would
be deemed to have occurred if the gaps and fissures through which smoke and gas
could pass are such as to lead to the ignition of a cotton pad placed opposite
the fissure. There is no doubt that a fissure of nominal 7 mm width would allow
sufficient leakage for ignition of the cotton pad, but in the case of a gap of
1½ mm it is most unlikely in our considered opinion that the leakage rate could
present this degree of problem.

Thus we see the two situations as being somewhat different and in the former
situation where the clearances range up to 7 mm the remedial measures are
specifically designed to preserve the fire resistance of the floor wall junction
taking into account that the floor will undergo further deflection under fire test
to a maximum of 1/30th of the span. In addition to the sealing for fire resistance
purposes the introduction of the mastic will ensure that in the developing stages
of a fire in the flat below, the products of combustion do not dissipate into
the flat above. In the latter case we consider that the introduction of the
mastic material, which in turn will be cloaked by the timber cover fillet would
control the leakage of smoke and hot gas from the flat below and certainly the
fire resistance would be preserved.

[handwritten annotation: what about the filling in the joint.]

London Borough of Newham
A16 FCA/IC
4 May 1984

Thus in terms of compliance with fire resistance requirements we would consider
the proposed remedial measures to be adequate and furthermore we would consider
that the introduction of the mastic materials as depicted on the sketches
referred to above, would control any leakage from fire in the flat below
particularly during the developing stages, and although this could be shown to
be unnecessary purely from the fire resistance aspect, we would nevertheless
consider that it is a wise precaution. In respect of the lounge situation, the
remedial measures that we have agreed to would, in our view, be satisfactory
for tolerances between the wall panel and the floor up to nominally 10 mm.

In respect of the application of the remedial work we would recommend that the
steel components should be fitted with considerable care to ensure that the
25 mm of ceramic fibre blanket is adequately compressed to the nominally 19 mm
and fitting the steel sections in relatively short lengths of 1200 mm would
enable the contour of the inner face of the wall panel to be followed fairly
closely. The positioning of the steel angle section, which is fixed to the
infill concrete is therefore of importance and adequate site supervision should
be used to check this detail.

I have signed and dated copies of the drawings submitted to be read in association
with this letter.

Yours faithfully

F C ADAMS

Encs:

WESA_1_11_04p1
8 of 13