Description of Ronan Point

6 DESCIPTION OF RONAN POINT
SUMMARY
The structural investigations of Ronan Point were primarily concerned with the as-
built condition of the structure, consideration of any aspects affecting its stability
under normal loading and under accidental gas explosion or fire loading, the
mechanism of movement of the non structural cladding panels, and remedial
actions considered to be appropriate. Later investigations were carried out to
cover an economic assessment of the services and overall refurbishment costs.
Ronan Point is one of nine similar blocks of 23 storeys, each providing 110 flats,
built by Taylor Woodrow Anglian in Canning Town, using the Larsen Nielson
industrialised system of large panel construction. All blocks have the same floor
plan and external appearance but there are significant differences between the two
basic types;
Type A: Ronan, Abrahams, Merrit, Gannon, Dodson and Bauckham Points.
Type B: Ault, John Sopp and Hume Points.
Type A were modified after the gas explosion in Ronan Point in 1968 to provide a
resistance to an explosion of equivalent static pressure of 2.5 lbs/sq.in. Piped gas
supplies were removed from these buildings.
Type B were built to a revised design with major revisions to joint details to
provide for a static pressure of 5 lbs/sq.in. They do contain piped gas installations
now converted to North Sea Gas.
Extensive investigations have been carried out during the period April-October
1984 at Ronan Point, covering: external surveys for fabric condition and physical
alignment; internal cuttings to check as-built details; materials tests; dynamic
testing by BRE; ultra-sonic survey of joints and structural panels; radar survey of
flank wall joints; exposure of flank wall joints; experimental fire and subsequent
load test; monitoring effect of underfloor heating and internal survey of lift
shaft.
Some fifty data reports were prepared and issued in draft form progressively in the
course of the works; abstracts of these reports are included in Section 3 and final
data reports are appended under separate cover.
Further services investigations covered the Heating and Ventilation systems,
plumbing, electrical services, thermal insulation, refuse disposal, fittings and
finishes, acoustics and lifts.
This report makes reference to three previous reports, summaries of which are
included in Appendices A, B and C. The principal conclusions listed in Section 4 are
briefly as follows:-
Flank Walls: Significant defects were found at Ronan Point. In our opinion, if
similar defects exist in the other five Type 'A' blocks, major repair works would be
required before the buildings could be considered to have adequate structural
strength in the long term, particularly in regard to overall behaviour in the event
of severe fire or gas explosion. Strengthening would involve the provision of a
steel frame at each of the two flank walls tied through the building within the floor
screeds. In view of noise and disturbance of tenants, if they remained in occupation
it may be considered appropriate to evacuate the building first. To improve safety
during the period prior to completion of the work it is recommended that
lower floors be vacated first and protected to eliminate the risk of fires at these
levels and that the risk of gas explosion be removed by ensuring that no gas
cylinders are brought into the building. It must be noted that the flank wall joints
as built to revised details for the Type "B" buildings are significantly stronger and
the above considerations are not applicable for these later buildings. Investigations
of the Type 'B' buildings are in progress and will be reported separately.
Cladding Panels: Some components of the cladding panels would be overstressed
under high wind loading and additional bolted connections are required. Cladding
movements should be restrained or accommodated in the design of the fire stop.
Overall Refurbishment Costs: Many items of essential refurbishment work to
structure, finishes, fittings and services were identified and the cost of these
estimated at £3,144,000 per block, a cost per housing unit of £28,600. With the
inclusion of desirable works these totals would increase to £5,724,000 per block and
cost per housing unit of £52,000. The Council's officers advised that the estimated
cost of demolition is £500,000 per block with replacement housing units estimated
at £45,000 each.
In regard to the Type B buildings it is noted that the structural joints are
fundamentally different from those of Type A (being less prone to imperfect
workmanship, less sensitive to defects and more robust) and the
considerations arising from the Ronan Point investigation are not applicable.
An investigation of Hume Point is in hand and will be reported separately.
4.2 Primary Structure
The flank wall joints are defective in respect of the hand packed mortar and
insitu concrete components of the joint. The resultant high stresses and
uncertain joint action require that major remedial works be undertaken
before the building can be considered to have adequate structural strength.
No test evidence for the behaviour of the flank wall joint under high vertical
loads and subject to local deformation and defective workmanship has been
found. Account needs to be taken of effects of fire, explosion and extreme
wind.
Recommendation: strengthening frames to be constructed at the flank
walls, tied through the building with ties buried in the floor screeds.
4.3 Cladding Panels
The bowing of the panels is attributable to two components: differential
shrinkage effects which are virtually complete and differential temperature
effects which give rise to daily and seasonal variations with movements of
up to 2mm.
Some components of the cladding panels would be overstressed under certain
conditions of wind loading.
Recommendation: that additional bolted connections be provided. Cladding
movements to be restrained or alternatively accommodated in the fire stop
detail. (See 4.4).
4.4 Fire Hazards
There are possible fire and fume paths caused by the bowing of the face
panels, minor fire hazards such as faulty fire doors and defects in
ventilation ducting.
35
4.0 CONCLUSIONS AND RECOMMENDATIONS
4.1 General
4.1.1 The conclusions and recommendations given below are consolidated from the
separate reports (summaries of which are appended) and are based upon the
investigations carried out in the period April to October 1984. While the
investigations have been taken far enough to enable general conclusions to
be drawn they have, of necessity, not been exhaustive. This Report,
therefore, does not consitute a warranty as to the soundness or
satisfactoriness of any parts of the building which have not been open to
inspection and whose condition cannot be ascertained before they are
completely opened up. Moreover, this Report is not intended to, and does
not, contain guidance on the stability of particular structural elements
under forces to which they may be subjected during any subsequent
renovation, rehabilitation or repair works.
4.1.2 Ronan Point is one of nine similar blocks built by Taylor Woodrow Anglian in
Canning Town. All blocks have the same floor plan and external appearance
but there are significant differences between two basic types:-
Type A: Ronan, Abrahams, Merrit, Gannon, Dodson and Bauckham
Points.
Type B: Ault, John Sopp and Hume Points.
Type A were modified after the gas explosion in Ronan Point in 1968 to
provide a resistance to an explosion of equivalent static pressure of
2.5 lbs/sq.in. Piped gas supplies were removed from these buildings.
Type B were built to a revised design with major revisions to joint details to
provide for a static pressure of 5 lbs/sq.in. They do contain piped gas
installations now converted to North Sea Gas.
If it is confirmed that the deficiencies identified at Ronan Point are all
present to the same degree in the other five Type A buildings the conclusions
and recommendations from this Report may be considered to be appropriate
for these Type A buildings.