Department of the Environment Press Notice, 'Ronan Point'

Department of the Environment
2 Marsham Street
London SW1P 3EB
Telephone 01-212 3434
Press Notice 471 23 October 1984
RONAN POINT: MINISTER WARNS AGAINST USE OF LIQUEFIED PETROLEUM GAS IN
CERTAIN BLOCKS OF FLATS OF MORE THAN 4 STOREYS BUILT IN LARGE-PANEL SYSTEMS
Ian Gow, Minister for Housing and Construction, has commented on the implications
of recent engineering studies of Ronan Point, Canning Town, for other buildings of
large panel construction and has reiterated earlier advice that, because of the
possible consequences of explosion, liquefied petroleum gas (LPG) cylinders should
not be used or stored in certain blocks of more than 4 storeys in height.
In reply to a Parliamentary Question from Nigel Spearing, MP (Newham South), who
had asked what reports the Secretary of State had received from the London Borough
of Newham concerning the condition of Ronan Point and similar tower blocks built in
the Taylor-Woodrow Anglian system, and what action he was taking in respect of such
blocks built in Newham and elsewhere, Mr Gow said:-
" In order to understand the implications of the reports
received by the London Borough of Newham for Ronan Point and
other large-panel blocks of flats it is necessary to take
account of the events of 1968 and subsequent action by the
Government and local authorities.
Background: Events in 1968 and immediately thereafter
In 1968 Ronan Point, a tower block built in the
Taylor Woodrow Anglian system, suffered a partial collapse.
The subsequent Tribunal of Inquiry in its report, 'Collapse of
Flats at Ronan Point, Canning Town' (HMSO 1968), found that an
explosion of town gas blew out concrete panels forming part of
the load-bearing flank wall of one flat. As a result, there
was progressive collapse of the south-east corner of the block.
The Tribunal made a series of recommendations affecting
system-built blocks of flats over 6 storeys in height. These
included measures to strengthen Ronan Point itself; measures to
appraise and, if needed, to strengthen existing buildings; and
measures to be taken into account in designing new buildings.
In addition there were interim recommendations about gas
disconnection.
Following these recommendations the then Ministry of
Housing and Local Government issued advice to local authorities
in Circulars 62/68 and 71/68.
The advice to authorities was to appraise all their blocks
over 6 storeys in height which were built of large pre-cast
concrete panels to form load bearing walls or floors or both in
order to consider whether they were susceptible to progressive
collapse. In considering whether strengthening was necessary
(either by providing alternative paths of support to carry the
load, assuming the removal of a critical section of the load-
bearing walls or by producing a form of construction of such
stiffness and continuity so as to ensure the stability of the
building against forces liable to damage the load supporting
members), they were to provide for forces equivalent to a standard
static pressure of 5 lbs per square inch (p.s.i) where town gas
was to be used. Where it was not to be used, the forces could be
halved, ie. to an equivalent of 2½ p.s.i of standard static
pressure.
As far as can be ascertained the Ministry did not ask authorities
to inform it of the appraisals or specific action taken in respect
of each block. It is known however that in many cases buildings
existing at the time or under construction were strengthened only
to resist forces of 2½ p.s.i and gas was not reconnected.
Ronan Point and 5 similar blocks existing or under construction
at the time of the explosion in 1968 were strengthened to resist
pressures of 2½ p.s.i by the addition of mechanical connections
to the joints between the flank walls and floor panels; and
a structural screed was added to the floor slabs adjacent to the
flank walls.
The report of the Inquiry (paragraph 173) warned in
specific terms about the dangers of storing explosive substances
such as liquefied petroleum gas (LPG) in such blocks as this
warning was repeated in more general terms in paragraph 13 of
Circular 62/68.
Events in 1984
Following observation of small gaps at the junctions between
non-load-bearing cladding panels of the facade and the floor
panels in Ronan Point, the London Borough of Newham decided
earlier this year to evacuate the block and in March it appointed
Building Design Partnership (BDP) to investigate this problem
and to report on any defects and incipient or actual fabric
deterioration. In April the brief was extended to include
investigations of the structure of Ronan Point in its current
condition with reference to structural stability, including
resistance to wind, gas explosion and the effects of fire.
Subsequently the Council appointed a second firm of consultants,
Thomas Akroyd and retained the Building Research Establishment
(BRE) to carry out dynamic tests and fire tests.
In July wide publicity was given to the results of a fire
test in an empty flat by the BRE. The purpose of the fire was
to test the effectiveness of a fire-stop detail designed by BRE
to fill the gaps between the cladding and the floors described
in paragraph 6 above and to prevent the spread of flame and fumes
from a flat subject to a fire to the flat above. Limits were
set on the permitted movement of ceiling panels to prevent
unnecessary structural damage to the flat in which the test was
arranged and as a safeguard for those observing the test. These
limits were reached after about 10 minutes (the fire was
deliberately very severe) and the test was stopped although the
severity of the fire was beginning to decline and it is unlikely
that further structural deformation would have occurred. The
detail proved generally satisfactory although a small quantity
of fumes penetrated the upper flat.
Nevertheless considerable local concern was generated by
reports of the fire test and Newham Council arranged for the
results to be presented to a public meeting on 4 August which was
attended by a representative of the Department as well as by the
Head of BRE's Fire Research Station. Subsequently Newham's
Housing Committee decided to continue the programme of tests,
which was not complete, and in response to demands that tenants
of the other 8 Taylor Woodrow Anglian blocks in the vicinity of
Ronan Point should be rehoused, decided that priority should
continue to be given to rehousing elderly and disabled tenants.
Investigation by the consultants continued and at the end
of September both BDP and Thomas Akroyd submitted reports to the
Council, copies of which have been made available to the Department.
These reports consider the findings of the investigations to date.
In particular they have found voids in the dry-pack mortar and
in situ concrete in some of the 'H.2' joints between the load-bearing
flank walls and the floor panels. They examined the question of the
likely behaviour of those joints in the context of the effects of
wind, fire and explosion.
Both BDP and Thomas Akroyd consider that Ronan Point is not
likely to be adversely affected by anticipated wind pressures,
eg. gales such as could occur once in 100 years, but could be
seriously damaged by an explosion, eg. arising from the storage
or use of LPG cylinders (there is no piped gas supply in
Ronan Point and the 5 similar blocks). They also agree that there
is a need for an effective fire-stop detail. BDP consider that
in the event of a very severe fire in 2 adjoining rooms, the
strengthened H.2 joint would be subject to 'stress levels not
previously experienced and therefore unproven'. Thomas Akroyd
concluded that the fire resistence of the various parts of the
structure is in accordance with the structural fire resistance
required for such concrete buildings.
The BRE is evaluating these reports and discussing them
with the consultants as a matter of urgency. Its provisional
view is that the risk that progressive collapse of the building
(as opposed to localised failure) could be caused by fire is
remote. Nevertheless, it considers that it is necessary to
investigate more fully what if any measures are necessary if
buildings of this type are to remain in satisfactory structural
condition in the longer term.
The London Borough of Newham shortly after receiving the
consultants' reports decided to rehouse tenants from the
5 Taylor Woodrow Anglian blocks in Canning Town, of the same
design as Ronan Point and 3 Taylor Woodrow Anglian blocks of the
more recent revised design, over an expected period of about
a year pending decisions about the long term future of the blocks
and meanwhile to continue the programme of investigations
and tests.
Advice to Owners and Government Action
Although difficult technical issues are involved, I am
concerned that the extent of partially-informed comment on these
events in recent weeks may be causing some local authorities
and their tenants undue anxieties. I have considered the advice
so far available to me and have decided to take the action set
out in the following paragraphs.
First I do not consider that the findings at Ronan Point
to date need cause other owners of blocks constructed in the same
or other large panel system to contemplate immediate rehousing
of residents or that they justify conclusions on the long term
future of such blocks. Each authority must of course make its
own management decision in the light of all the relevant
circumstances.
Second authorities should consider urgently practical steps
to prevent the use and storage of LPG cyclinders or other
explosive materials in:
a. All blocks over 6 storeys in height built of large
pre-cast concrete panels to form load-bearing walls or
floors, or both, not designed or strengthened to resist
a standard static pressure of 5 p.s.i (mains gas should
have been disconnected from such buildings).
b. Any other blocks, whether of flats or houses, which
do not satisfy the requirements of section D17 of the
Building Regulations, which applies to buildings having
5 or more storeys (including basement storeys, if any).
The advice on blocks over 6 storeys essentially reiterates the
advice given in the Inquiry report, MHLG Circular 62/68, the
Home Office's Fire Prevention Guide No.4, 'The safe use and
storage of liquefied petroleum gas in residential premises'
(HMSO 1976) and the second annual report of the Engineering
Institutions' Standing Committee on Structural Safety
(Chairman, Lord Penney) in 1978.
The advice on other blocks is a reflection of the fact
that progressive collapse could occur in certain buildings of
less than 7 storeys. It should be noted that in 1978 the
principal suppliers of LPG advised their agents not to make
cylinders of LPG available to customers in blocks of flats and
maisonettes of more than 4 storeys whatever their form of
construction. The Department has evidence that despite these
warnings the use of LPG heaters by tenants is increasing.
Third the BRE is devoting and will devote whatever resources
are necessary to investigate as a matter of urgency the problems
highlighted at Ronan Point and to provide advice on structural
appraisal and remedial measures as necessary. This will involve
a significant input of resources by the BRE into the problems of
large panel systems of construction. The Department intends to
discuss the formulation of this programme of work with the local
authority associations as soon as the immediate work by BRE on
Ronan Point makes it possible.
Further guidance to owners of Taylor Woodrow Anglian
buildings will be issued in the light of BRE's evaluation of the
evidence.
The Department will be writing this week to inform local
authorities of the action which we consider owners of dwellings
of large-panel construction ought to take now, to give further
details of the action which might be taken on LPG, and to ask for
any technical reports and information which authorities may have
on large-panel buildings in their ownership. A copy of the
Department's letter will be placed in the Library."