Department of the Environment
2 Marsham Street
London SW1P 3EB
Telephone 01-212 3434

Press Notice  71           19 February 1985

RONAN POINT - SUMMARY OF BRE FINDINGS ANNOUNCED

Ian Gow, Minister for Housing and Construction announced today that an independent
assessment by the Building Research Establishment (BRE) had found certain weaknesses
in the construction of Ronan Point, a 22 storey tower block in the London Borough of
Newham and the BRE's findings on Ronan Point are likely to apply to some degree to
other Taylor Woodrow Anglian buildings. The Department of the Environment has today
written to those local authorities which own Taylor Woodrow Anglian buildings to
inform them of the action considered necessary.

In a written answer to a Parliamentary Question from Nigel Spearing MP, (Newham
South), Mr Gow said:

"The Building Research Establishment (BRE) has examined reports prepared for the
London Borough of Newham by the Building Design Partnership and Thomas Akroyd and for
the Newham Tower Blocks Tenants' Association by Mr Sam Webb. It has also made its
own assessment of the structural behaviour of Ronan Point under the loads, both
normal and abnormal, to which the building might be subject. The BRE's report of its
assessment will be published as soon as possible.

"The BRE concludes that, although Ronan Point has since 1968 carried all the
loads, including high wind loads, to which it has been subject and that these loads
have approached the maximum which it might be expected to encounter, without showing
any signs of distress, the ends of the H2 joints in the flank walls of the lower
storeys of the building do not provide that wide margin of safety which is generally
considered acceptable for buildings of this type.

"The BRE has considered the likely performance of Ronan Point under abnormal
loads such as could be caused by an explosion or fire. Though explosion in any
building may cause serious damage, the BRE concludes that, in view of the measures
taken already to strengthen the building, the risk that an explosion could cause
progressive collapse of Ronan Point, such as occurred in 1968, is remote, provided
steps are taken to prevent the use of liquified petroleum gas for heating. The BRE
concludes that it is extremely unlikely that such collapse could be caused by fire.

more ...

"The BRE considers that the gaps which occur at junctions between cladding panels and floor slabs are unacceptable since they could allow the spread of fire and fumes between adjacent flats.

"The BRE concludes that certain remedial works are necessary at Ronan Point.

"The conclusions drawn from the assessment of Ronan Point are likely to apply in some degree to other Taylor Woodrow Anglian buildings, depending on the details of the construction in each case. Proper standards of safety should apply in all these buildings. In particular, all Taylor Woodrow Anglian buildings of 14 or more storeys in height which the H2 joints are of the same design as those in Ronan Point should be appraised to establish whether these joints provide adequate margins of safety.

"All Taylor Woodrow Anglian buildings should be appraised to establish whether the joints between panels can resist the spread of fire and fumes adequately.

"The BRE is ready to discuss with authorities methods of inspection and appraisal and the extent to which its conclusions apply to particular Taylor Woodrow Anglian buildings.

"The Department is writing today to those authorities which own Taylor Woodrow Anglian buildings to inform them of the action which we consider necessary. Copies of the Department's letter are being placed in the library."

NOTES TO EDITORS

Ronan Point, and other Taylor Woodrow Anglian buildings, are made of large prefabricated reinforced panels.

In 1969 Ronan Point suffered a partial collapse. A subsequent Tribunal of Inquiry found that an explosion of town gas blew out concrete panels forming part of the load-bearing flank wall of one flat and, as a result, there was progressive collapse of the south-east corner of the block.

In 1984, gaps were found at the junction between non load-bearing cladding panels and floor slabs at Ronan Point. This junction is known as the H1 joint. In the course of subsequent investigations commissioned by the London Borough of Newham, it was found that some of the joints between load-bearing external wall panels and floor slabs had not been properly made. This joint is known as the H2 joint.

On 23 October 1984 the Minister for Housing and Construction, in a statement to Parliament, drawing attention to the Department's assessment of the implications of these findings said that:

more ...

1. he did not consider that the findings at that time needed to cause other
owners of large panel blocks to contemplate immediate rehousing of tenants
or that they justified conclusions on the long-term future of such buildings;

2. authorities should consider urgently practical steps to prevent the use
and storage of liquified petroleum gas cylinders because of the possible
consequences of explosion;

3. that the BRE was to urgently investigate the problems highlighted at
Ronan Point and provide advice on structural appraisal and remedial measures
to local authorities as necessary.

The Department's records show that 90 high rise blocks of flats were built
in England in the Taylor Woodrow Anglian system. Of these 20 blocks (including
Ronan Point) are of fourteen or more storeys and have H2 joints of the same
design as those in Ronan Point.