TBUK6018

Sam Webb, Drawing, Taylor Woodrow-Anglian/Larsen Nielsen System, Flank Wall to Floor Joint Loadbearing, H2

ARCHIVE DOCUMENT
Not stated
March 1985
Start of document

HAND-DRAWN diagrams
Title: ORIGINAL LARSEN & NIELSEN SYSTEM JOINT FLANK WALL TO FLOOR JOINT LOADBEARING

CROSSWALL & LOADBEARING FLANK WALL JOINTS
CROSSWALL
LOADBEARING PANEL
NON LOADBEARING OUTER FACE
NEOPRENE BAFFLE WEATHER SEAL
POLYSTYRENE INSULATION
DRY PACK
WATERPROOF PACKING
FLOOR SCREED
SKIRTING
FLOORSLAB
HOLLOW CORE
CENTRE LINE OF LIFTING BOLT
LOAD BEARING NIB
INSITU CONCRETE
LEVELLING NUT & LIFTING BOLT
DETAILS FROM "LARGE PANEL CONSTRUCTION: SOME GENERAL CONSIDERATIONS" D. BISHOP AMICE ARICS BUILDING RESEARCH STN OCT 1962 2 3/4" 68
DRY PACK
INSITU CONCRETE
FLANK WALL TO FLOOR JOINT

NOTE
THE FLOOR SLAB BEARS A FULL 3" 75 mm ONTO THE TOP OF THE LOADBEARING PANEL. THE DRYPACK IS FULLY RESTRAINED BY THE TOP OF THE OUTER LEAF OF THE WALL PANEL. THE JOINT IS NOT DESIGNED TO TAKE BENDING MOMENTS. ALL LOADS ARE ASSUMED TO BE ACTING IN COMPRESSION OTHERWISE ROTATION WILL OCCUR AT THE END OF THE FLOORSLAB. THE ONLY RESISTANCE TO PREVENT THIS IS THE POLYSTYRENE INSULATION. THERE IS NO STEEL IN THE JOINT WHICH IS FOR A LOWRISE BUILDING.

SAM WEBB RIBA MARCH 1985
H2

End of document
TBUK6018