TBUK15034

National Tower Blocks Network, Annual Spot Safety Survey

ARCHIVE DOCUMENT
Not stated
November 1990

PART ONE

NATIONAL IMPLICATIONS OF MERRY HILL COURT FIRE

Our information indicates that the fire in Merry Hill Court was
serious because of two main factors. First structural defects in the
block caused the fire to spread rapidly. Second, the condition of the
means of escape and of fire fighting equipment within the block
endangered tenants lives and delayed and impeded the rescue work.

The information included here has come from a variety of sources
but it is by no means definitive as we await the publication of a full
and comprehensive official report.

1. STRUCTURAL DEFECTS

* The fire in July was the second within seven months. The fire
enquiry, into the previous fire in January 1990 revealed that there
were no fire stops between each flat. The gaps, surrounding a gas
duct, had instead been filled with newspaper. The gas pipes
themselves were also not fire proof - they had been boxed in using
plywood.

* The flats in Merry Hill Court were therefore not separate
compartments as the building regulations require. They could not
contain a fire for one hour and thus allow tenants time to escape.

* The fire on the 13th July spread rapidly over 6 floors, through
this duct, trapping tenant Jennifer Noble.

2. FIRE FIGHTING/MEANS OF ESCAPE

* The dry riser main within the block which is designed to allow
the fire brigade to pump water up to any landing wasn't working.
Water had to be pumped from a nearby canal.

* Defective fire doors onto the staircase (the means of escape)
allowed smoke and fumes to enter.

3. BREACH OF BRITISH STANDARD CODE OF PRACTICE

The above factors show that Merry Hill Court failed to comply with
the British Standard Code of Practice CP3: Chap1V (1962)
Precaution against Fire. The Code states:

"The assumption should no longer be made that buildings must be
evacuated if a fire occurs and high residential buildings should,
therefore, be designed so that the occupants of floors above a
dwelling which is on fire may, if they choose, remain safely on
their own floor. It may be necessary to evacuate the floor on which
the fire occurs, and in some circumstances those floors which are
in the immediate vicinity of the fire, but the occupants of these
floors should be free to reach safety in any part of the building via
the staircase."

"It is, of course, essential that there should be adequate physical
separation between the two occupancies and that the means of
escape from the dwellings should be designed and constructed so
that they can under no circumstances be attacked by fire or smoke
from the other occupancy."

"The guiding principle in the recommendations which follow is
safety of life. In securing this, means of escape, construction and
firefighting all play a part. This part of the Code deals with all
three subjects, but recommendations on constructions have not
been fully developed as many aspects are already subject to
building control." Quote from the Introduction of Chap IV (1962).

4. NATIONAL INSPECTIONS

* After the fire Brian Fuller, the Chief Fire Officer for the West
Midlands Fire Service advised the Chief Executive of all tower block
owning local authorities to inspect their blocks for the above
problems. The West Midlands Fire Service have also carried out
their own inspection of tower blocks within their district. The
extent and the results of these investigations are still not yet
publicly known more than 4 months on.

* NTBN's discussions with fire officers have raised some serious
questions. In particular the decision by the London Fire Brigade in
April 1990 to cease carrying out annual 'wet tests' on dry riser
mains in tower blocks. This inspection involved a practical test of
the main, using a fire engine to create the appropriate pressure
which was measured on the roof. This test ensured that water could
be pumped to every floor in a fire. We have been informed that the
testing was stopped as a result of spending restrictions imposed on
the London Fire Service.