TBUK15022

National Tower Blocks Network, Fire Safety Information Pack

ARCHIVE DOCUMENT
Not stated
1990

BUILDING REGULATIONS

The construction of buildings in England and Wales is covered by a number of different sets of Building Regulations, Acts of Parliament, the British Standards Codes of Practice (BSCP) and the British Standards (BS). The regulations discussed in this report refer to the construction of tower blocks.

LAWS FOR LONDON
The regulations governing Inner London are made under the London Buildings Acts 1930-39 and are all enforced by the District Surveyor. Section 20 of the London Buildings Acts refers to a building over 100 feet in height or having a large internal volume, which applies to most tower blocks within Inner London. There was a need for the cut-off point because fire brigade ladders can only reach a certain height.

Blocks in Inner London also need to comply with one of the following codes:
BSCP CP3 Chap IV (1962): Fire precautions in flats and maisonettes above 80’ in height. (The 80’ refers to the height of a fire brigade ladder.)
BSCP CP3 Chap IV (1971): Fire precautions in flats and maisonettes above three storeys in height.

WHAT THEY SAY
The basic requirements of CP3 Chap IV (1962) are that each flat should be, capable of containing a fire for the minimum period of one hour. Any duct passing through a flat should have a one hour fire stop. The walls of the duct should also be capable of containing the fire for the same period. The 1971 code introduced the additional requirement of an alternative means of escape from each flat or maisonette.

In Outer London, England and Wales tower blocks must comply with one of these codes depending on when the block was built. Most were built when the 1962 code was in force, but any subsequent alterations or improvements to the blocks may need to meet the regulations as defined in the 1971 code.

IF YOU ARE OUTSIDE LONDON
In addition to these codes the Building Regulations England and Wales apply outside Inner London. They first came into force on February 1st 1966 and were amended in 1972. Before 1966 blocks were built under a number of Metropolitan Regulations, usually based on the Model Byelaws of 1953. These would have been enforced by the Building Inspectors now known as Building Control Officers.

CHANGING LEGISLATION
Building regulations are constantly being changed and updated. When a new regulation is made law, it only applies to buildings that are being refurbished or new builds. The latest is BS 5588 Part 1 1990.

This new standard highlights methods of preventing the spread of fire, which includes the spread of smoke. Refurbishment work to be carried out on blocks in one part of Sheffield are being brought up to this new standard (see p. 22).

TBUK15022
22 of 57