Ronan Point Investigation

SUMMARY
S1 Introduction
The current investigations of Ronan Point are primarily concerned with:-
- the as-built condition of the structure
- consideration of any aspects affecting its stability under normal
loading and under accidental gas explosion or fire loading
- the mechanism of movement of the non-structural cladding panels,
and
- remedial actions considered to be appropriate
Ronan Point is one of nine similar blocks of 23 storeys, each providing 110
flats, built by Taylor Woodrow Anglian in Canning Town. All blocks have the
same floor plan and external appearance but there are significant
differences between two basic types.
Type A: Ronan, Abrahams, Merrit, Gannon, Dodson and Bauckham
Points.
Type B: Ault, John Sopp and Hume Points
Type A were modified after the gas explosion in Ronan Point in 1968 to
provide a resistance to an explosion of equivalent static pressure of 2.5
lbs/sq.in. Piped gas supplies were removed from these buildings.
Type B were built to a revised design with major revisions to joint details to
provide for a static pressure of 5 lbs/sq.in. They do contain piped gas
installations now converted to North Sea gas.
1
S2 General Investigations
Extensive investigations have been carried out at Ronan Point:-
- External surveys for fabric condition and physical alignment,
including bowing
- Internal cuttings to check as built details
- Materials Tests
- Dynamic Testing by BRE
- Ultra-sonic survey of joints and structural panels
- Radar survey of flank wall joints
- Exposure of flank wall joints
- Experimental fire and subsequent load test
- Monitoring effect of under floor heating
- Internal survey of lift shaft
Over thirty data reports have been produced and the results are referred to
in this report. Additionally archive information has been sorted and indexed.
S3 Defects and Recommendations for Repair
With the important exception of the first two items listed below, the
investigations have found that the construction accords with the drawings;
some deterioration of the fabric but no deterioration of structural
components has been observed. The following defects have been found,
requiring repair or remedial action.
S3.1 Flank Wall/Floor Joints Defects:-
- the horizontal hand packed mortar joints between precast panels
above floor levels are significantly voided.
- the insitu concrete filling betwen the precast panel and the floor
edge is poorly compacted and voids occur underneath the lower
reinforcement bar.
- levelling nuts have not been wound down after hand packing the joints
and stresses in the lifting bolts have caused cracking in the precast
units local to the bolts.
Analysis of the effects of these defects indicates there are zones of very
high stress and uncertainty in the transmission of forces through the various
components of the joints. It is considered that as a result of these defects
the bolted connections added for the purpose of explosion resistance are
required for security under normal loading conditions and the security of the
joint under the effects of fire is uncertain.
The defects are such that, in our opinion, major repair works are required
before the building can be considered to have adequate structural strength
in the long term.
Implications in other Type A Buildings
It first needs to be confirmed that the defects encountered in Ronan Point
are also present in the other five buildings. This could be simply investigated
using Radar equipment from suspended cradles on the external faces of the
flank walls.
The structural strengthening required to meet long term requirements would
involve work within the building. Because of the noise and disturbance to the
tenants if they remained in occupation, it may be considered appropriate to
evacuate the building first.
The actions required, therefore, would be of two categories: those
necessary to ensure adequate safety during a reasonable and orderly
decanting of the tenants during, say a 12-18 month period, and those
necessary to provide for the longer term, say the next thirty years.
The strength of the building has proved adequate for all loading conditions
experienced since construction.
The possible hazards not previously experienced by the building during the
next 12-18 months are:
3
1. Unusually high, say 1 in 100 year, gales.
Calculations indicate that the increased stresses over those already
experienced would be in the order of 5%. The basic behaviour mode
of the joint would not be affected. We do not consider that the flank
wall joints are particularly sensitive to a marginal increase in stress
providing the behaviour mode is unchanged.
2. Major fires causing high thermal movements.
As a result of horizontal displacement and rotation of the joint
caused by thermal expansion, the behaviour mode would be changed
with significant transfer of vertical load from one section of the joint
to another section which is as yet unproved and possibly defective.
This factor would be most serious in the more highly loaded wall
joints of the lower floors. The risks would be substantially reduced if
the lower floors were to be vacated first, thereby eliminating the risk
of fires at these levels.
3. Gas explosions.
The risk of gas explosions during the decanting period of 12-18
months should be removed by ensuring that no gas cylinders are
brought into the building.
Remedial Works to Flank Wall Joints in Type A Buildings
The detailing of the horizontal flank wall joint is such that satisfactory
repairs to the defects would be difficult to effect. We recommend that
structural strengthening frames be constructed at the flank walls, detailed
to collect the floor loadings, and adequately tied through the building with
ties buried in the depth of the floor screeds. Such structural frames would
not only provide adequate structural strength for all existing loads, but
could be designed to increase the permissible explosion loading from 2½ psi
to 5 psi (for which the Type B blocks were designed).
The adoption of such a structural solution would, no doubt, be considered
along with other environmental options in assessing the viability of retaining
or replacing these housing units.
For Type B buildings, the insitu flank wall joints are much bigger, contain
interlocking reinforcement connecting the units and vibrated concrete was
specified and practical. Such joints will accept eccentric loading and are
less sensitive to any deficiencies which may exist in the hand packed joints,
providing that the insitu concrete is confirmed to be solid. The condition of
the joints should be checked. If defects exist it is likely that they can be
simply repaired.
The considerations above for Type 'A' blocks are not applicable for the Type
'B' buildings.
S3.2 Non-Structural Cladding Panels
The non load-bearing cladding panels are in our view, over-stressed under
high local wind loading usually considered in current practice in respect of
the transom zone, connections to the building and connections between the
two leaves of the panel. The recommendations for strengthening these
connections involve the addition of bolts which could be installed from the
outside of the building.
S3.3 Lift Shafts
Local zones of incomplete hand packed mortar were observed in the joints
of the lift shaft walls. Calculations indicate that the mortar is not
significantly over-stressed. Simple repairs to complete the mortar filling by
hand packing from the inside of the shaft are required.
S3.4 Mosaic Faced Panels
Local repairs are required to make good zones of loose or missing mosaics
and to repair a few instances of damage to corners of panels.
S3.5 Exposed Aggregate Panels
The exposed aggregate panels forming the outer leaf of the flank walls are
in generally good condition but an instance of corrosion damage was
observed. In order to arrest penetration of carbonation and protect in the
long term against the onset of corrosion in zones where cover to
reinforcement is low a protective coating is advisable.